![Daikin REYQ8-48PY1B Скачать руководство пользователя страница 379](http://html.mh-extra.com/html/daikin/reyq8-48py1b/reyq8-48py1b_service-manual_502202379.webp)
SiBE37-701_B
Troubleshooting by Indication on the Remote Controller
Troubleshooting
368
3.59
“
UF
”
System is not Set yet
Remote
Controller
Display
UF
Applicable
Models
All indoor unit models
REYQ8P~48P
Method of
Malfunction
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to
that of indoor units that have made changes in temperature.
Malfunction
Decision
Conditions
The malfunction is determined as soon as the abnormality aforementioned is detected through
checking the system for any erroneous connection of units on the check operation.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-
outdoor units
Failure to execute check operation
Defect of indoor unit PCB
Stop valve is left in closed
Troubleshooting
Note:
Wiring check operation may not be successful if carried out after the outdoor unit has been off
for more than 12 hours, or if it is not carried out after running all connected indoor units in the
fan mode for at least an hour.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
Are the stop valves
opened?
Open the stop valve.
NO
NO
YES
YES
YES
NO
Is the check
operation carried
out?
Is indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
Is indoor-outdoor and
outdoor-outdoor unit
transmission wiring
normal?
Replace the indoor unit PCB.
After fixing the incorrect
wiring, push and hold the
RESET button on the master
outdoor unit PCB for 5
seconds.
* The unit will not run for up to
12 minutes.
Wiring check operation may
not have been carried out
successfully.
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...