Troubleshooting by Indication on the Remote Controller
SiBE37-701_B
367
Troubleshooting
Troubleshooting
Correct the wiring.
YES
NO
Check the
transmission
wiring between
centralized
controller for any
broken wire. (
∗
1)
A
YES
NO
Abnormal
Normal
Has the master unit
central setting connector
been connected?
Disconnect the transmission wiring
of the master unit centralized
controller, and then check the
voltage between the transmission
terminals (F1 and F2) of the
master unit transmission
equipment using a multiple meter.
Is the voltage
between the terminals
F1 (+) and F2 (-) in
the range of 15.2 to
17.6 VDC?
Correct the connection of the
connector.
Replace the central
equipment.
Centralized controller: Normal
It is supposed that the
malfunction results from
external factors (e.g. noises)
from other equipment.
∗
1 For details, refer to information in the “Procedure for checking broken wires” section. (Refer to P387)