Outline of Control (Indoor Unit)
SiBE37-701_B
153
Function
6.8
Hot Start Control (In Heating Operation Only)
At startup with thermostat ON or after the completion of defrosting in heating operation, the
indoor unit fan is controlled to prevent cold air from blasting out and ensure startup capacity.
[Detail of operation]
When either the
start
condition 1
or the
start
condition 2
is established, the operations shown
below will be conducted.
TH
2
: Temperature (°C) detected with the gas thermistor
TC
: High pressure equivalent saturated temperature
Defrost ending or oil return ending
or Thermostat ON
Hot start ending conditions
OR
·
lapse of 3 minutes
·
[TH2]>34°C
·
"Tc">52°C
Hot start control
Hot start in progress
Fa
n
H/L remote
controller setting
H/L remote
controller setting
LL
OFF
Remote controller
setting
Po (Horizontal)
Lo
uv
er
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
Normal control
Normal control