SiBE37-701_B
Troubleshooting by Indication on the Remote Controller
Troubleshooting
308
3.30
“
J4
”
Outdoor Unit: Malfunction of Temperature Sensor
for Heat Exchanger Gas (R2T or R11T)
Remote
Controller
Display
J4
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Detect malfunction based on the temperature detected by each thermistor.
Malfunction
Decision
Conditions
In operation, when a thermistor is disconnected or short circuits.
Supposed
Causes
Defective connection of thermistor
Defective thermistor
Defective outdoor unit PCB
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P450.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector is
connected to X30A
of outdoor PCB
(A1P).
NO
Connect the connector and turn on
again.
Confirm which thermistor is
abnormal using outdoor unit
"monitor mode".
(Refer to P.255~P.256)
Resistance is normal
when measured after
disconnecting the
thermistor (R2T or
R11T) from the
outdoor unit PCB.
(1.8k
Ω
to 800k
Ω
)
YES
NO
YES
Replace the thermistor (R2T or
R11T)
Replace the outdoor unit PCB
(A1P).
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...