Special Control
SiBE37-701_B
125
Function
Cooling indoor unit actuator
Oil return operation
Fan
Thermo. ON unit
Remote controller setting
Unit not in operation
OFF
Thermo. OFF unit
Remote controller setting
Electronic expansion
valve
Thermo. ON unit
Normal opening degree
Unit not in operation
192pls
Thermo. OFF unit
Normal opening degree for forced thermostat ON
Heating indoor unit actuator
Oil return operation
Fan
Thermo. ON unit
Remote controller setting
Unit not in operation
OFF
Thermo. OFF unit
Remote controller setting
Electronic expansion valve
Thermo. ON unit
Normal opening degree
Unit not in operation
224 pls
Thermo. OFF unit
Normal opening degree for forced thermostat ON
Cooling BS unit actuator
Elect. symbol
Oil return operation
Electronic expansion valve (EVH)
Y4E
0pls
Electronic expansion valve (EVL)
Y5E
760pls
Electronic expansion valve (EVHS)
Y2E
0pls (60pls when Pc
_
max>2.85MPa)
Electronic expansion valve (EVLS)
Y3E
480pls
Electronic expansion valve (EVSC)
Y1E
PI control
Heating BS unit actuator
Elect. symbol
Oil return operation
Electronic expansion valve (EVH)
Y4E
760pls
Electronic expansion valve (EVL)
Y5E
0pls
Electronic expansion valve (EVHS)
Y2E
60pls
Electronic expansion valve (EVLS)
Y3E
0pls (60pls when Pc
_
max>2.85MPa)
Electronic expansion valve (EVSC)
Y1E
PI control
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...