Field Setting
SiBE37-701_B
193
Test Operation
3.1.2 Wireless Remote Controller - Indoor Unit
BRC7C type
BRC7E type
BRC4C type
1. When in the normal mode, push the “
” button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the “
” button.
3. Pushing the “
” button, select the first code No.
4. Pushing the “
” button, select the second code No.
5. Push the timer “
” button and check the settings.
6. Push the “
” button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0” and second code No. to “02”.
MODE NO.
FIELD SET MODE
3
4
5
SECOND CODE NO.
FIRST CODE NO.
2
1, 6
(V2770)