![Daikin REYQ8-48PY1B Скачать руководство пользователя страница 327](http://html.mh-extra.com/html/daikin/reyq8-48py1b/reyq8-48py1b_service-manual_502202327.webp)
SiBE37-701_B
Troubleshooting by Indication on the Remote Controller
Troubleshooting
316
3.37
“
JC
”
Outdoor Unit: Malfunction of Low Pressure Sensor
Remote
Controller
Display
JC
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the low pressure sensor.
Malfunction
Decision
Conditions
When the low pressure sensor is short circuit or open circuit.
(Not less than 1.77MPa, or -0.01MPa and below)
Supposed
Causes
Defect of low pressure sensor system
Connection of high pressure sensor with wrong connection.
Defect of outdoor unit PCB.
Defective connection of low pressure sensor
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are the characteristics of the low
pressure sensor normal? (Make
a comparison between the
voltage characteristics (
∗
1) and
the gauge pressure.)
NO
Replace the low pressure sensor.
Confirm which high pressure
sensor is abnormal using
outdoor unit "monitor mode".
(Refer to P.255~P.256)
1. Set the low pressure gauge
upright.
2. Connect the checker for
VRV to the gauge.
If the PCB pressure
detection normal? (Make a
comparison between the
checker pressure data and
the voltage characteristics
(
∗
1).)
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of
the low pressure
sensor normal?
Replace the main PCB.
Replace the low pressure sensor.
Replace the main PCB.
NO
NO
YES
YES
YES
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...