SiBE37-701_B
Field Setting
Test Operation
234
k
Cancel disabling the outdoor unit 2 from operating:
Set No. 39 "Disable-outdoor-unit-2 operation" of setting mode 2 to "OFF".
k
Cancel disabling the outdoor unit 3 from operating:
Set No. 40 "Disable-outdoor-unit-3 operation" of setting mode 2 to "OFF".
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 39
times.
k k h h k k k
(3) Press the CHECK button (BS3) once.
k h h h h l h
(4) Press the OPERATE button (BS2) once.
k h h h h h l
(Factory setting)
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 40
times.
k k h k h h h
(3) Press the CHECK button (BS3) once.
k h h h h l h
(4) Press the OPERATE button (BS2) once.
k h h h h h l
(Factory setting)
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h