SiBE37-701_B
Protection Control
Function
138
[Inverter fin temperature control]
★
Perform the following control of integrated as well as multi units for each INV compressor.
Normal operation
Tfin>84°C
&
• Tfin<81°C
• INV upper limit frequency=max (210Hz)
During the control of fin
temperature protection
INV Comp. upper limit step:
1-step down
Tfin>84°C
• 10 seconds
Current status
maintained
Tfin<81°C
continues for 3 minutes
INV Comp. upper limit
step: 1-step up
Tfin>93°C
Fin temperature standby
When occurring 4 times within 60 min.,
the malfunction code “L4” is output.