Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
394
[Check 14] List of inverter-related malfunction codes
Code
Name
Condition for determining malfunction
Major cause
Comp
ressor
cu
rrent
L5
Instantaneous overcurrent of
inverter compressor
• Inverter output current exceeds 32.3A even
instantaneously.
• Liquid sealing
• Faulty compressor
• Faulty inverter PCB
L8
Overcurrent of inverter
compressor (Electronic thermal)
• Compressor overload running
An overcurrent of 19.0A or more continues for
a period of 5 consecutive seconds or that of
16.1A or more continues for a period of 260
consecutive seconds.
• The inverter loses synchronization.
• Backflow of compressor liquid
• Sudden changes in loads
• Disconnected compressor wiring
• Faulty inverter PCB
P
rot
ec
ti
on d
e
vi
ce
and ot
hers
L1
Faulty inverter PCB
• No output is given.
• Faulty heavy current part of
compressor
L9
Faulty startup of inverter
compressor
• The compressor motor fails to start up.
• Liquid sealing or faulty
compressor
• Excessive oil or refrigerant
• Faulty inverter PCB
E5
Inverter compressor lock
• The compressor is in the locked status (does
not rotate).
• Faulty compressor
L4
Radiator fin temperature rise
• The radiator fin temperature reaches 87°C or
more (while in operation).
• Malfunction of fan
• Running in overload for an
extended period of time
• Faulty inverter PCB
U2
Power supply voltage error
• The inverter power supply voltage is high or
low.
• Power supply error
• Faulty inverter PCB
P1
Imbalanced power supply
• Power supply voltages get significantly
imbalanced among three phases.
• Power supply error (imbalanced
voltages of 2% or more)
• Faulty inverter PCB
• Dead inverter PCB
LC
Transmission error (between
inverter PCB and control PCB)
• With the outdoor unit PCB, no
communications are carried out across control
PCB - inverter PCB - fan PCB.
• Broken wire in communication
line
• Faulty control PCB
• Faulty inverter PCB
• Faulty fan PCB
PJ
PCB mismatching
• Any PCB of specification different from that of
the product is connected.
• PCB of different specification
mounted
P4
Faulty fin thermistor
• The fin thermistor gets short-circuited or open. • Faulty fin thermistor
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...