Field Setting
SiBE37-701_B
191
Test Operation
3. Field Setting
3.1
Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
3.1.1 Wired Remote Controller <BRC1E51>
<Basic screen>
(1)
<Field setting menu screen>
(2)
Press Menu/Enter button.
<Field setting screen>
In the case of individual
setting per indoor unit
In the case of group total
setting
(3)
(4)
(5)
(3)
(5)
SECOND CODE NO.
FIRST CODE (SW) NO.
Press Menu/Enter button.
1
Press and hold Cancel button for
4 seconds or more.
Field setting menu is displayed.
2
Select
Field setting list
in the
field setting menu, and press
Menu/Enter button.
Field setting list screen is displayed.
3
Highlight the mode, and select
desired “Mode No.” by using
(Up/Down) button.
4
In the case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE NO. “ - ” means no
function.
Highlight SECOND CODE NO. of
the FIRST CODE NO. to be
changed, and select desired
“SECOND CODE NO.” by using
(Up/Down) button. Multiple
identical mode number settings
are available.
5
In the case of group total
setting, all of SECOND CODE
NO. which may be set are
displayed as “
∗
”. “
∗
” is
changed to SECOND CODE
NO. to be set. And, SECOND
CODE NO. “ - ” means no
function.
In the case of setting per indoor
unit during group control (When
Mode No. such as
20
,
21
,
22
,
23
,
25
are selected), highlight
the unit No. and select “Indoor
unit No.” to be set by using
(Up/Down) button.
(In the case of group total setting,
this operation is not needed.)
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...