Troubleshooting by Indication on the Remote Controller
SiBE37-701_B
337
Troubleshooting
3.46
“
PJ
”
Outdoor Unit: Faulty Field Setting after Replacing
Main PCB or Faulty Combination of PCB
Remote
Controller
Display
PJ
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
This malfunction is detected according to communications with the inverter.
Malfunction
Decision
Conditions
Make judgment according to communication data on whether or not the type of the inverter PCB
is correct.
Supposed
Causes
Faulty (or no) field setting after replacing main PCB
Mismatching of type of PCB