Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
388
[CHECK 8] Master Unit Central Connector Setting Table
The master unit central setting connector (CN1/X1A) is mounted at the factory.
•
To independently use a single unit of the intelligent Touch Controller or a single unit of the
centralized remote controller, do not dismount the master unit central setting connector (i.e.,
use the connector with the factory setting unchanged).
•
To independently use the schedule timer, insert an independent-use setting connector.
No independent-use setting connector has been mounted at the factory. Insert the
connector, which is attached to the casing of the main unit, in the PCB (CN1/X1A).
(Independent-use connector=Master unit central setting connector)
•
To use two or more centralized controller in combination, make settings according to the
table shown below.
(*1) The intelligent Touch Controller and the schedule timer are not available for combined use.
(*2) The intelligent Touch Controller, centralized remote controller, and the unified ON/OFF controller have been set to "Provided with the
master unit central setting connector" at the factory. The schedule timer has been set to "Not provided with the master unit central
setting connector" at the factory, which is attached to the casing of the main unit.
Pattern
Centralized controller connection pattern
Setting of master unit central setting connector (*2)
intelligent
Touch
Controller
Centralized
remote
controller
Unified
ON/OFF
controller
Schedule
timer
intelligent
Touch
Controller
Centralized
remote
controller
Unified ON/
OFF
controller
Schedule
timer
(1)
1 to 2
units
× (*1)
Only a
single unit:
"Provided",
Others:
"Not
provided"
(2)
1 unit
1 unit
× (*1)
Provided
Not
provided
(3)
1 to 8
units
× (*1)
All "Not
provided"
(4)
1 to 2
units
× (*1)
Only a
single unit:
"Provided",
Others:
"Not
provided"
(5)
1 to 4
units
Only a
single unit:
"Provided",
Others:
"Not
provided"
(6)
1 to 16
units
1 unit
All "Not
provided"
Not
provided
(7)
(8)
1 unit
Not
provided
(9)
1 to 16
units
Only a
single unit:
"Provided",
Others:
"Not
provided"
(10)
1 unit
Not
provided
(11)
1 unit
Provided
Содержание REYQ8-48PY1B
Страница 1: ...Service Manual REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701_B ...
Страница 456: ...Piping Installation Point SiBE37 701_B 445 Appendix ...
Страница 460: ...Example of connection SiBE37 701_B 449 Appendix ...
Страница 476: ...Revision History Date News No Contents 2010 9 10 M 10011 Correction of service manual ...