SiBE37-701_B
Troubleshooting by Indication on the Remote Controller
Troubleshooting
260
3.2
“
A1
”
Indoor Unit: PCB Defect
Remote
Controller
Display
A1
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Check data from E²PROM.
Malfunction
Decision
Conditions
When data could not be correctly received from the E²PROM
E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned off.
Supposed
Causes
Defect of indoor unit PCB
External factor (Noise, etc.)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The indoor unit PCB is
normal.
External factor other than
malfunction (for example,
noise etc.).
Replace the indoor unit PCB.
Turn power supply OFF, then
power ON again.
Does the
system return
to normal?
YES
NO