IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
89
Description
Enables the detection of missing other controllers on the CAN-B bus. If the
setpoint is in ENABLED position and there aren't any other controllers detected on
the CAN-B bus (the complete bus, not only within the logical group) the alarm
CAN-B Empty
is issued.
Setpoint: LB/UART Log
Group
Comms settings
Range [units]
DISABLED, ENABLED
Related FW
3.0
Force value
possible
YES
Force value
possible
YES
Description
The setpoint enables/disables logging of remote communication activity. If logging
is enabled connection and disconnection of each remote terminal as well as
entering access code are recorded into the history.
N
OTE
:
The terminal is disconnected automatically after 5 min of inactivity and next
communication request from the same terminal is considered as a new
connection. When logging is enabled in certain conditions the history may be filled
up with large number of records related to the communication and important
records may be overwritten quite fast.
Setpoint: CANAddrSwitch1
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
The setpoint selects function of the terminal address 122 at the (CAN-A) line. See
the latest communication guide for details about this topic.
MODEM
The address is used for modem connection via I-LB
OTHER
The address is used for direct connection to any other device as
e.g. IV8 or I-RD.
Setpoint: CANAddrSwitch2
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
The setpoint selects function of the terminal address 125 at the (CAN-A) line. See
the latest communication guide for details about this topic.