IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
86
N
OTE
:
The RS232 connector is no more available in hardware version 2.0 and above.
The COM2 port is redirected to the RS485(2) terminals all the time. That means
modem is not supported at COM2 in these hardware versions. For modem use
the COM1 port instead.
Setpoint: RS232(1)MBCSpd
Group
Comms settings
Range [units]
9600, 19200, 38400, 57600 [bps]
Related FW
3.0
Description
The setpoint adjusts the communication speed on the COM1 connector when it is
switched to MODBUS or MODBUS-MDM(HW) mode. See also the setpoint
Setpoint: RS232(2)MBCSpd
Group
Comms settings
Range [units]
9600, 19200, 38400, 57600 [bps]
Related FW
3.0
Description
The setpoint adjusts the communication speed on the COM2 connector when it is
switched to MODBUS or MODBUS-MDM(HW) mode. See also the setpoint
Setpoint: RS232(1)MdmIni
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
This setpoint can be used to add extra AT commands at the end of the
initialization sequence of the modem connected to the COM1 port. The command
can be entered with as well as without the "AT" prefix, are separated with
semicolon and maximal length is 31 characters.
The setpoint can't be modified via the IG-NT built-in terminal.
Setpoint: RS485(1) conv.
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Description
This setpoint selects function of the built-in RS485(1) converter.