DISABLED
Pressing of the fault reset button (at any terminal or external button) resets
only
inactive
alarms. Active alarms remain in the alarmlist unchanged and must be reset
again when they become inactive.
ENABLED
Pressing of the fault reset button (at any terminal or external button) resets
all
alarms that
are currently present in the alarm list. Inactive alarms disappear from the alarm list
immediately, active alarms are changed to "confirmed" state and disappear when the
alarm condition disappear or the alarm starts to be blocked.
N
OTE
:
ENABLED position corresponds to the method how the IG-classic and IS-classic controllers handled the
alarms.