IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
256
or virtual output terminal).
Alarm output: WrnVoltRegLim
Related FW
3.0
Description
This output is closed while the
WrnVoltRegLim
alarm is present in the alarm list,
i.e. while the analog output for AVR is near minimum or maximum position (out of
the range 2% to 98% for more than 2s).
N
OTE
:
This alarm is disabled when AVR control via binary outputs
AVR up
and
AVR dn
is used (i.e. at least one of these outputs is configured onto a physical or virtual
output terminal).
Alarm output: Sd Oil press B
Related FW
3.0
Description
This output is closed while the
Sd Oil press B
alarm is present in the alarm list, i.e.
while there is a mismatch between gen-set state (running/stopped) and position of
the input
Alarm output: OfL StartBlck
Related FW
3.0
Description
This output is closed while message
OfL StartBlck
is present in the alarm list. The
message indicates that the setpoints
Island enable
,
ParallelEnable
and
are adjusted in such a way, that the genset is not allowed to operate in
current conditions, for example if mains breaker is opened and however island
operation is disabled.
Alarm output: Start blocking
Related FW
3.0
Description
The output is closed while there is the message
Start blocking
in the alarm list, i.e.
while the input
Alarm output: Fuel theft
Related FW
3.0
Description
This output is closed while the
Fuel theft
alarm is present in the alarm list. This
alarm occurs when the fuel level value measured at the analog input
Fuel level
drops faster than is the limit adjusted by setpoint