IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
79
Range [units]
DISABLED,ENABLED [-]
Related FW
3.0
Force value
possible
YES
Description
This setpoint can be used to aviod possible unexpected automatic start of the
gen-set in AUT mode after the gen-set was stopped by a protection and then fault
reset was pressed.
ENABLED
The controller mode is automatically changed from any mode
except OFF to MAN if any red-level protection is
acknowledged by pressing of the fault reset.
DISABLED
The automatic change of the controller mode is disabled.
N
OTE
:
The function will not work if the current controller mode is forced by one of the
inputs
Remote AUT
or
Remote TEST
.
Setpoint: Local buttons
Group
Basic settings
Range [units]
PANEL, EXTBUTTONS, BOTH [-]
Related FW
3.0
Description
The setpoint selects which set of control buttons is currently active. Its function
depends on which type of controller is used. Please refer to the section which
suits your controller/display version.
•
First section deals with the case of IGS-NT with built-in monochrome
display.
•
Second section deals with the case of IGS-NT-BB with IV5 display.
•
Third section deals with the case of IGS-NT-BB with IV8.
N
OTE
:
If you have IGS-NT (built-in display) and you use additional IV display all the
sections may be relevant (depending on the type of additional displays).
IGS-NT (built-in monochrome display)
PANEL
The built-in buttons on the controller front panel (IG-NT) or
terminal #1 (IS-NT) are enabled, the binary inputs for
external buttons are disabled.
EXTBUTTONS
The built-in buttons are disabled and the binary inputs for
external buttons are enabled.
BOTH
Both built-in buttons and binary inputs for external buttons
are enabled.