IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
119
Setpoint: #RunHrsMaxDiff
Group
Pwr management
Range [units]
0 .. 65000 [h]
Related FW
3.0
Description
This setpoint adjusts the "deadband" for the
running hours equalization
function.
The priorities are swapped not until the relative engine hours (RHE) difference is
higher than this deadband.
Setpoint: #PwrBandContr 1
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#1 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter
Gen-set size optimalization
.
N
OTE
:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.
Setpoint: #PwrBandContr 2
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#2 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter
Gen-set size optimalization
.
N
OTE
:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.
Setpoint: #PwrBandContr 3
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#3 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter
Gen-set size optimalization
.
N
OTE
:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.