IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
107
Related FW
3.0
Description
This setpoint adjusts the delay for the generator current unbalance protection. The
threshold for the protection is adjusted by setpoint
N
OTE
:
The generator current unbalance protection is created in the default archive using
the mechanism of
universal analog protections
. That means
this setpoint is one
of general-purpose setpoints
, which may be used for different purpose if the
protection is deleted from the configuration.
Setpoint: Bus V unbal
Group
Bank protect
Range [units]
0 .. 200 [%]
Related FW
3.0
Description
This setpoint adjusts the threshold level for the bus voltage unbalance protection.
The threshold is adjusted in % of the nominal generator voltage, which is either
, depending on the position of the setpoint
. The protection
is created in the default archive as universal
analog protection
at the value
Bus V unbal
, which is calculated as maximum
difference between two bus phase voltages.
The protection activates if the voltage unbalance gets over the threshold for time
longer than
N
OTE
:
Activation of the protection is only recorded into the history file, no other actions
are performed.
N
OTE
:
The voltage unbalance protection is created in the default archive using the
mechanism of
universal analog protections
. That means
this setpoint is one of
general-purpose setpoints
, which may be used for different purpose if the
protection is deleted from the configuration.
Setpoint: Bus V unb del
Group
Bank protect
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay for the bus voltage unbalance protection. The
threshold for the protection is adjusted by setpoint
N
OTE
:
The bus voltage unbalance protection is created in the default archive using the
mechanism of
universal analog protections
. That means
this setpoint is one of
general-purpose setpoints
, which may be used for different purpose if the
protection is deleted from the configuration.