IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
181
Value: NumUnsc start
Group
Statistics
Units
-
Related FW
3.0
Description
Unsuccessful starts counter. The counter is incremented always when
Start fail
alarm is issued.
N
OTE
:
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
Value: Service time 1
Group
Statistics
Units
h
Related FW
3.0
Description
This is maintenance countdown timer #1. The timer is located in setpoints (group
Engine protect
) as well as in values (group
Statistics
). Adjust the timer to the
requested maintenance interval. It will be then decremented while the gen-set is
running. The alarm
WrnServiceTime
is issued as soon as the timer counts down
to zero.
Value: Service time 2
Group
Statistics
Units
h
Related FW
3.0
Description
This is maintenance countdown timer #2. The timer is located in setpoints (group
Engine protect
) as well as in values (group
Statistics
). Adjust the timer to the
requested maintenance interval. It will be then decremented while the gen-set is
running. The alarm
WrnServiceTime
is issued as soon as the timer counts down
to zero.
Value: Service time 3
Group
Statistics
Units
h
Related FW
3.0
Description
This is maintenance countdown timer #3. The timer is located in setpoints (group
Engine protect
) as well as in values (group
Statistics
). Adjust the timer to the
requested maintenance interval. It will be then decremented while the gen-set is
running. The alarm
WrnServiceTime
is issued as soon as the timer counts down
to zero.