105 

Description 

This setpoint adjusts the reaction time of the IDMT EarthFault Current protection if 
the current is 200% of the base level given by the setpoint 

Nom EthFltCurr

 

The reaction time of the IDMT EarthFault Current protection is not fixed; it depends 
on how much is the current above the limit (base level). The higher is the current 
the shorter the reaction time will be.  

 

E

XAMPLE OF 

IDMT

 CURRENT PROTECTION CURVE

 

 

N

OTE

:

 

 

The IDMT EarthFault Current protection is 

Breaker open and cool down (BOC)

 

type.  
 

N

OTE

:

 

 

This protection's internal counter accumulates and it starts continuously decreasing 
when the EarthFault Current goes below 

Nom EthFltCurr

. This function prevents 

the protection from completely reseting when the EarthFault Current goes below 

Nom EthFltCurr

 for only a short period of time. This behavior emulates circuit-

breaker with thermal current protection.  
 

 

Setpoint: Bank V unbal 

Group 

Bank protect 

Range [units] 

0 .. 200 [%] 

Related FW 

3.0 

Description 

This setpoint adjusts the threshold level for the generator voltage unbalance 
protection. The threshold is adjusted in % of the nominal generator voltage, which 
is either 

BankNomV

 or 

BankNomVph-ph

, depending on the position of the 

setpoint 

FixVoltProtSel

. The protection is 

Breaker open and cool down

 type and 

is 

created in the default archive as universal analog protection

 at the value 

Gen 

Содержание IG-NT GC

Страница 1: ...l info comap control com www comap control com REFERENCE GUIDE Compact Controller for Stand by and Parallel Operating Gen sets Inteli New Technology Modular Gen set Controller Bank Controller IG NT GC...

Страница 2: ...it breakers operation sequence CB fail detection 26 Remote Alarm Messaging 31 Controller Redundancy 32 Force value step by step guide 33 Values for continuous writing from external sources 35 General...

Страница 3: ...ce Guide PDF 3 Modbus protocol 61 Value and setpoint codes 61 Technical data 61 Language support 61 Setpoint groups 64 Table of setpoints 64 Table of values 151 Table of binary input functions 183 Tab...

Страница 4: ...zech Republic Phone 420 246 012 111 Fax 420 266 316 647 Web WWW COMAP CONTROL COM e mail info comap control com DOCUMENT HISTORY VERSION NUMBER RELATED SW VERSION DATE 1 1 2 0 31 3 2016 2 1 2 0 4 1 20...

Страница 5: ...nt list of all Setpoints Values Logical Binary Inputs and Logical Binary Output IGS NT COX 3 1 0 Reference Guide pdf General description of COX applications for InteliGen NT and InteliSys NT Contains...

Страница 6: ...START STOP or Disconnect output STARTER and outputs GCB CLOSE OPEN and MCB CLOSE OPEN The controller contains a large number of configurable setpoints because of this it is impossible to describe all...

Страница 7: ...nary outputs Starter and Fuel to avoid unexpected automatic start of gen set and GCB closing Clarification of notation HINT This type of paragraph points out details to help user installation configur...

Страница 8: ...ts a procedure adjustment etc which may cause damage or improper functioning of the equipment if not carried out correctly and may not be clear at first sight WARNING This type of paragraph indicates...

Страница 9: ...eBox IS BC MINT 1 2 0 ant Gen set Controller firmware hardware archive compatibility The subordinated Gen set controller has to be loaded with appropriate FW IGS NT 3 3 0 and higher The special XXX MI...

Страница 10: ...ion so that from the outside point of view the group behaves as one large gen set Bank controllers can be connected together so that large tree style multisites power stations can be created The aim o...

Страница 11: ...set controllers can use address 1 31 See the Figure CAN bus wiring NOTE The gen set controller is never connected directly to the CAN A but it has to be always subordinated to some BankController NOT...

Страница 12: ...er first starts the bank and when it is running the bank controller synchronizes the bank to the common bus This option is reccommended to be used whenever it is possible CAUTION Feeders and or mains...

Страница 13: ...1 2 0 ComAp January 2019 IGS NT BC 1 2 0 Reference Guide PDF 13 Figure Power line wiring of system with the BCB Figure Power line wiring of system without the BCB GC Gen set controller IG NT IS NT BC...

Страница 14: ...of wiring of the power lines see Power lines wiring paragraph above If BCB is used following AC values are to be measured Bank bus voltage 3phase required Common bus voltage 3phase required Bank curre...

Страница 15: ...EXTENSION MODULES INTERC ONTR OLLER MONITORI NG DISPLAY L H L H IS NT LB 9 BANK CONTROLLER k L2 L3 L1 L2 L3 GENERATOR VOLTAGE MAINS VOLTAGE L1 L2 L3 TO OTHER GENSET BANKS COMMON BUSBAR BANK BUSBAR TO...

Страница 16: ...T1A fuses for controller voltage measurement circuits protection BCB control and synchronizing If the system is equipped with BCB the BCB is controlled by the Bank controller There is a set of contro...

Страница 17: ...mon bus as soon as all the available gensets in the bank are running If there is countervoltage on the common bus the breaker is synchronized otherwise it is closed to the dead bus In automatic mode t...

Страница 18: ...oad and requested load reserve are started setpoint Powermanagement Pwr management is set as ENABLED The power management can be based on kW kVA or on relative reserve The start of the bank is a 1 sec...

Страница 19: ...NT must be connected on the CAN2 to control gen set group kW I E Important setpoints ProcessControl SysLdCtrlPtM LDSHARING Import Export power factor Gen set group is controlled to keep constant or ad...

Страница 20: ...ed gen set groups CAN segments to ensure the equal distribution of the load On the top of it it performs the inter bank powermanagement In the same time the second level of power management is perform...

Страница 21: ...the banks and between the ge sets can be set differently Sum of available nominal power running gen sets in PM Total Load of the system Starting sequence Stopping sequence Bank 1 Priority 1 Bank 2 Pr...

Страница 22: ...tion relevant to the actual load Thanks to the Automatic priority swapping function the Bank Controllers choose the banks to be running with consideration of their average running hours and the actual...

Страница 23: ...BandContr2 PwrBandContr3 and PwrBandContr4 The load levels of the power bands are defined by sum of available nominal powers of banks that are adjusted to run in each particular power band and the loa...

Страница 24: ...s have to work independently The group which the particular controller belongs to is adjusted by the setpoint Pwr management Control group If there is only one group in the site adjust the setpoint to...

Страница 25: ...EM AUT mode b When MCB opens from parallel to mains operation in SEM AUT mode c Before MCB is opened in MAN mode by button The load shedding function is active in all controller modes except OFF Load...

Страница 26: ...Load reconnection manual AutoLd recon DISABLED BO Load shed 2 Ld recon level Gen set power BO Load shed 3 BO Load shed 1 BI Man load recon opened opened opened no action Circuit breakers operation seq...

Страница 27: ...CB UV coil output for undervoltage coil of the CB Permanently active 2s negative pulse 5s if synchronising is not provided by the particuilar CB is used for CB opening request CB status output indica...

Страница 28: ...uld be issued after the second unsuccessfull attempt BO CB status 0 BI CB fdb neg 1 BI CB fdb 0 BO CB fail ON pulse has finished and CB status is not 1 CB fail is issued immediatelly 2s BO CB OFF coil...

Страница 29: ...db BO CB close open BO CB UV coil During CB opening the CB status LBO is deactivated with change of the first feddback status Further behavior of UV output depends on the system status In case of tran...

Страница 30: ...il BI CB fdb neg BI CB fdb BO CB close open BO CB UV coil BO CB status BO CB ON coil Closing pulse is shortened opening sequence is started immediatelly CB opening by protection or manual command butt...

Страница 31: ...em An analog modem must be connected either to one of controller COM ports or to one of I LB modules connected to the controller via CAN2 bus The channel address must contain complete telephone number...

Страница 32: ...possible to adjust number of attempts that controller performs in case of not successful Active Call Comms settings ActCallAttempt The language of messages can be changed Comms settings Acall SMS lan...

Страница 33: ...nce the failed controller may not interpret it correctly VPIO VPI VPO CtrlHBeat FD Emerg manual CAN LOG BOUT LOG BIN Watched contr X Setpoint Emerg manual LOG BIN CAN BOUT BIN LOG BIN MAIN CONTROLLER...

Страница 34: ...tc Select source setpoint or value For example if we add Force value Force value 1 to be forced to ProcessControl Export limit as value 0 DISABLED by Binary Input FORCEVALUEIN 1 we can change the func...

Страница 35: ...o damage may occur External values are reverted back to their default initial value given by corresponding setpoint when Binary Input for their reset is active and they change to the previous value af...

Страница 36: ...s repeated with adjusted period hh mm The timer duration is included in the preriod The mode of each timer channel is adjusted by an assigned setpoint The setpoints are located int the Timer settings...

Страница 37: ...ucture 4 Fast history separator The fast part is located above the separator 5 Estimated number of records depending on record size 6 Record capacity usage indicator NOTE Values that are displayed in...

Страница 38: ...tton is this function mapped to 0 first button 1 second button and so on Choose UserButton index and its function ON OFF etc Choose which colour will be available for this button Select which conditio...

Страница 39: ...rtual Peripheral Inputs Outputs can be added to configuration and it will copy the state of Remote Switch on virtual output to its counterpart virtual input Refer to the figure below for example LBO R...

Страница 40: ...es between all the controllers via CAN bus thus saving physical Inputs and Outputs and excess wiring Figure Adding of various modules SHBOUT 1 SHBIN 1 SHBOUT 2 Not Received Module SHBIN 2 is not inser...

Страница 41: ...and are distributed among all controller in the system including all controllers connected to CAN A or CAN B like described by the Figure Virtual shared signals in the system with bank controller NOT...

Страница 42: ...ller Up to 32 DISTBIN modules can be configured meaning that the controller will be receiving all DISTBOUT from all the controller even his own It is not possible to change the name of DISTBIN inputs...

Страница 43: ...a CAN1 can be used For more information on how to use this module please refer to InteliGen InteliSys Communication Guide and to I CBEdit manual User MODBUS Users can define Modbus registers from 4287...

Страница 44: ...ister port for writing Input value LBO ModbusSw16 ModbusSw1 ModbusSw1 46337 000F HEX 0000 0000 0000 1111 Register port for writing Input value LBO ModbusSw32 ModbusSw17 ModbusSw2 46338 F000 HEX 1111 0...

Страница 45: ...sions in which values and some setpoints are interpreted or adjusted Power formats may be changed in Miscellaneous tab in GenConfig There are following Power Formats available 1 kW kVAr kVA kX V 0 1 k...

Страница 46: ...Sys Start Stop Sys S S from IM2 BTB feedback Sys S S from IM1 M2 Start sheet output Sys S S from IM1 BTB feedback Sys S S from IM2 M1 Start sheet output Shared binary inputs Logical Group 2 Logical G...

Страница 47: ...controllers support up to five Languages that is possible to switch during controller duty Every terminal i e Remote display or PC InteliMonitor can be switched to different language Use PC GenConfig...

Страница 48: ...omAp January 2019 IGS NT BC 1 2 0 Reference Guide PDF 48 Frequency select 1500 1800 Preheat request Yes No Protection override Yes No Engine params Bin selector x Bin selector x CAN J1939 Force value...

Страница 49: ...citation Loss 46 Current Unbalance 47 Voltage Assymetry 47 Phase Rotation 50 51 Overcurrent 50N 64 Earth Fault Current 51N 64 Earth Fault Current IDMT 55 Power Factor 59 Overvoltage 71 Gas Fuel Level...

Страница 50: ...ks the internal signal Sys start stop to subordinated gen sets is deactivated The bank can t be started again while there is a Shutdown alarm in the Alarmlist Activates the output Common Sd as well as...

Страница 51: ...ediate stop of the banks the internal signal Sys start stop to subordinated gen sets is deactivated The gen set can t be started again while there is a BOC alarm in the Alarmlist Activates the output...

Страница 52: ...1 is not active The evaluation begins ForceBlockDel1 seconds after the input has been deactivated Force block 2 The alarms are beeing evaluated while the input Force block 2 is not active The evaluati...

Страница 53: ...the engine because of them If the input is deactivated and some protections are still active or not yet reset the controller starts to take these protections into account and consequently stops the e...

Страница 54: ...perating states Protections evaluation depends on the gen set state depends on the actual gen set conditions Configuration of User configurable protections in GenConfig It is possible to configure pro...

Страница 55: ...figurable protection Open Protections tab in GenCofig and adjust parameters that are described below Existing custom protections list Add protection Delete protection Select the value for the protecti...

Страница 56: ...hen they become inactive ENABLED Pressing of the fault reset button at any terminal or external button resets all alarms that are currently present in the alarm list Inactive alarms disappear from the...

Страница 57: ...teliIO8 8 8 8 2 InteliIO16 0 16 0 2 I CB x x x x Configurable communication bridge IGL RA15 15 15 Green Red Yellow LED panel I AOUT8 8 8 Analog outputs VPIO 8 8 Virtual periphery I O module SHBIN 8 SH...

Страница 58: ...onfiguration requires the highest password 7 level so only User 0 is able to modify the controller configuration or firmware Continuous internal evaluation of setpoints validity In case of detection o...

Страница 59: ...IGS NT BC SW Version 1 2 0 ComAp January 2019 IGS NT BC 1 2 0 Reference Guide PDF 59 List of possible events The complete list is available in Troubleshooting guide...

Страница 60: ...d free GND terminal is not connected 5 GND 2 RxD 3 TxD PC 5 GND 2 RxD 3 TxD RS232 RS232 230 VAC 0 VDC CONTROLLER Battery Required the same voltage potential between GND s RS 232 GenConfig functions Ex...

Страница 61: ...cation speed The delay is not shorter than the time needed to send receive 3 and characters The complete description of Modbus communication protocol can be found in Modbus Protocol Reference Guide PI...

Страница 62: ...lay from firmware version 1 5 supports following language code pages Code page Language Windows code 0 West European languages Windows 1252 134 Chinese GB 2312 162 Turkish Windows 1254 129 Korean Wind...

Страница 63: ...IGS NT BC SW Version 1 2 0 ComAp January 2019 IGS NT BC 1 2 0 Reference Guide PDF 63 APPENDIX...

Страница 64: ...s of all available setpoints values logical binary inputs and logical binary outputs that you can find in next chapters are common for standard gen set in MINT application and the Bank Controller For...

Страница 65: ...0 99L 1 01 1 20 correspond to capacitive PF 0 99C 0 80C NOTE sign in the name of this setpoint marks that this setpoint is shared among all controllers connected by CAN2 bus Setpoint SysLdCtrl PtM Gr...

Страница 66: ...adjusted by the logical functional analog input MLC AnExSysBld NOTE If the external source is selected the logical analog input must be configured at each gen set to the identical source The shared pe...

Страница 67: ...point is used for adjusting the starting point of the Power derating 1 function where the gen set nominal power is still 100 of the setpoint Nomin power See the chapter Power derating for details NOTE...

Страница 68: ...tarting point of the Power derating 2 function where the gen set nominal power is still 100 of the setpoint Nomin power See the chapter Power derating for details NOTE The setpoint actual physical dim...

Страница 69: ...n NONE No synchronizing is enabled FORWARD GCB synchronizing is enabled REVERSE MCB synchronizing is enabled BOTH GCB and MCB synchronizing are enabled NOTE Although synchronizing of the particular br...

Страница 70: ...ired for this function PRINCIPIAL SCHEME OF A SITE IF NEUTRAL CONT EACH The COMMON option should be used if there is one common neutral contactor for the whole site The outputs Neutral CB C O from all...

Страница 71: ...roller to specify the address of the related main controller in CAN based rendundant systems Adjust this setpoint to 0 if the controller is not used as redundant or if wired rendundancy system is used...

Страница 72: ...T ratio sec Group Basic settings Range units 5A 1A Related FW 3 0 Description Nominal current of the secondary side of the generator current transformers The primary side is adjusted by setpoint CT ra...

Страница 73: ...st the generator voltage transformers ratio NOTE Adjust the setpoint to the value of 1 0 if the generator voltage is connected directly to the controller terminals i e without transformers NOTE Exampl...

Страница 74: ...asurement The range 120V is intended for high voltage applications where voltage transformers with 100V secondary range are used or for alternative American 120V measurement Setpoint Vb InpRangeSel Gr...

Страница 75: ...int is used to adjust the nominal rated generator voltage phase to phase This setpoint is also recalculated automatically when the phase neutral nominal voltage BankNomV is changed This setpoint can b...

Страница 76: ...MP 97 hence the desired values are reached Setpoint BusNomVph ph Group Basic settings Range units 17 60000 V Related FW 3 0 Description In application MINT and COX This setpoint is used to adjust the...

Страница 77: ...s nominal phase phase voltage is 400V measured voltages are L12 400V L23 390V L31 390V the L23 and L31 are at 97 5 of the nominal It is obvious that if the situation is evaluated from phase neutral vo...

Страница 78: ...set is started and stopped only manually using START and STOP buttons or external buttons wired to appropiate binary inputs however the the full start sequence up to the moment when the engine is load...

Страница 79: ...XTBUTTONS BOTH Related FW 3 0 Description The setpoint selects which set of control buttons is currently active Its function depends on which type of controller is used Please refer to the section whi...

Страница 80: ...n orange box depends on functions assigned to each button individually If any function in the list in the note below is assigned to these buttons then it behaves as buttons in the red box if any other...

Страница 81: ...s as buttons in the green box The binary inputs for external buttons are affected in the same way as in the case of IGS NT built in monochrome display by this setpoint NOTE In the case that more IV di...

Страница 82: ...e of increasing of the PulseCounter 1 module The module counts pulses at the input PulseCounter 1 and if the input pulses counter reaches value given by this setpoint the counter value PulseCounter 1...

Страница 83: ...group Statistic is increased by 1 and input pulses counter is reset to 0 Both counter value and input pulses counter are stored in the nonvolatile memory Group Comms settings Setpoint Gen set name Gr...

Страница 84: ...er Communication DIRECT Connection to a local PC via RS232 or RS485 with internal or external converter interface Use this option also for IG IB connected via RS232 cable The internal RS485 converter...

Страница 85: ...EM HW Modem point to point connection to a remote PC with hardware data flow control using signals RTS CTS Full modem cable is required for this option MODEM SW Modem point to point connection to a re...

Страница 86: ...CSpd Group Comms settings Range units 9600 19200 38400 57600 bps Related FW 3 0 Description The setpoint adjusts the communication speed on the COM2 connector when it is switched to MODBUS or MODBUS M...

Страница 87: ...ated FW 3 0 Description This setpoint can be used to add extra AT commands at the end of the initialization sequence of the modem connected to the COM2 port The command can be entered with as well as...

Страница 88: ...rollers CAN bus length limited up to 900 meters Change of this setpoint is applied after the controller is switched off and on again NOTE Use low speed for long distance connection only Set all connec...

Страница 89: ...al is disconnected automatically after 5 min of inactivity and next communication request from the same terminal is considered as a new connection When logging is enabled in certain conditions the his...

Страница 90: ...usted FIXED The ethernet connection is adjusted fixedly according to the setpoints IP address Net mask Gateway IP DNS IP This method should be used for classic ethernet or Internet connection When thi...

Страница 91: ...is setpoint is used to adjust the IP address of the gateway of the network segment where the controller is connected In Automatic settings mode this setpoint is used to display the gateway IP address...

Страница 92: ...a connection to the Internet The AirGate server address is adjusted by the setpoint AirGate addr Setpoint AirGate IP Group Comms settings Range units max 32 characters Related FW 3 0 Description This...

Страница 93: ...39 109 of the SMTP server Please ask your internet provider or IT manager for this information NOTE You may also use one of free SMTP servers e g smtp gmail com However please note that some free SMTP...

Страница 94: ...Range units Related FW 3 0 Description In fixed settings mode this setpoint is used to adjust the domain name server DNS which is needed to traslate domain names in e mail addresses and server names...

Страница 95: ...tie breakers position Normally a collision would be indicated if there were more sources on the bus and this setpoint can be used to disable the evaluation of collisions in this special case Group Co...

Страница 96: ...t is adjusted to OFF the horn output is not activated at all the NO TIMEOUT position means the horn output is not deactivated until the alarms are reset Setpoint BinInp delay 1 Group Engine protect Ra...

Страница 97: ...uts can have either fixed 0 5s evaluation delay or there are three independent delay setpoints and one of them can be assigned to each particular binary input protection Setpoint ForceBlockDel1 Group...

Страница 98: ...NABLED Pressing of the fault reset button at any terminal or external button resets all alarms that are currently present in the alarm list Inactive alarms disappear from the alarm list immediately ac...

Страница 99: ...e after the gen set is synchronized to the mains i e the Warming load can be adjusted also below the sepoint Min Power PtM This setpoint is also used as the requested load level if a protection of Low...

Страница 100: ...od of the generator voltage The period is either 0 02s for 50Hz systems or 0 0166s for 60Hz systems E g if the delay is set to 0 03s at 50Hz system the real delay will be 0 04s Setpoint 2Inom del Grou...

Страница 101: ...ion which is adjusted by setpoint Bank V Sd NOTE The BOC protections are active after the Max stab time elapsed or after the GCB was closed then while the GCB is closed and then also during cooling if...

Страница 102: ...tended to be used as first level protection with lower threshold whereas the shutdown one is intended as second level with higher threshold Setpoint Bank V del Group Bank protect Range units 0 00 600...

Страница 103: ...tection activates if the frequency in phase L3 drops below the threshold for time longer than Bank f del NOTE The generator underfrequency protection is Breaker open and cool down BOC type NOTE The BO...

Страница 104: ...0 s Related FW 3 0 Description The setpoint adjusts the delay for generator reverse power protection The threshold for the protection is adjusted by setpoint Reverse power Setpoint Nom EthFltCurr Gro...

Страница 105: ...ernal counter accumulates and it starts continuously decreasing when the EarthFault Current goes below Nom EthFltCurr This function prevents the protection from completely reseting when the EarthFault...

Страница 106: ...sm of universal analog protections That means this setpoint is one of general purpose setpoints which may be used for different purpose if the protection is deleted from the configuration Setpoint Ban...

Страница 107: ...iversal analog protection at the value Bus V unbal which is calculated as maximum difference between two bus phase voltages The protection activates if the voltage unbalance gets over the threshold fo...

Страница 108: ...wer management mode ABS KW The power management is based on actual active power and gen set nominal power The reserves are calculated and adjusted in kW ABS KVA The power management is based on actual...

Страница 109: ...please use IGS NT PSC firmware in additional controller more information about this FW can be found on our webpages www comap cz Note that this priority swapping function may be used only if Pwr mgmt...

Страница 110: ...master role Setpoint SysAMFstrtDel Group Pwr management Range units 0 600 s Related FW 3 0 Description This setpoint adjusts the delay between closing of the input Sys start stop and activation of th...

Страница 111: ...me situations to allow genset start after Sys Start Stop gets active It is not destined for normal operation Please refer to the Troubleshooting guide for more information chapter MGCB is not closed a...

Страница 112: ...dResStop 2 Group Pwr Management Range units LoadResStrt 2 32000 kX Related FW 3 0 Description This setpoint is used to adjust the load reserve for stop in absolute mode i e Pwr mgmt mode ABS kW or ABS...

Страница 113: ...nputs is active the set 1 is selected NOTE The reserve for stop must be always adjusted higher than the reserve for start Setpoint LoadResStrt 4 Group Pwr Management Range units 32000 LoadResStop 4 kX...

Страница 114: ...Strt 1 Group Pwr Management Range units 0 LdResStop 1 Related FW 3 0 Description This setpoint is used to adjust the load reserve for start in relative mode i e Pwr mgmt mode REL if the reserve set 1...

Страница 115: ...in the chapter Reserves minimal running power The currently active reserve set is selected by binary inputs Load res 2 Load res 3 and Load res 4 If none of these inputs is active the set 1 is selecte...

Страница 116: ...binary inputs Load res 2 Load res 3 and Load res 4 If none of these inputs is active the set 1 is selected Setpoint LdResStop 4 Group Pwr Management Range units LdResStrt 4 110 Related FW 3 0 Descript...

Страница 117: ...speed up the start up of the next gen set NOTE The setpoint takes place only in island operation Setpoint NextStopDel Group Pwr Management Range units 0 3600 s Related FW 3 0 Description This setpoint...

Страница 118: ...are 3 different MinRunPower setpoints this particular one is activated by the input MinRun power 2 NOTE If more than one binary input for MinRunPower activation is closed MinRunPower with higher numbe...

Страница 119: ...be created so that the total nominal power of the Power band 1 2 3 4 Setpoint PwrBandContr 2 Group Pwr management Range units 1 2 1 2 3 1 3 2 3 1 2 3 Related FW 3 0 Description This setpoint is used t...

Страница 120: ...0 Description This setpoint is used for adjusting the delay of changing the power band if the load demand rose above the upper limit of the current power band Learn more about this topis in the chapte...

Страница 121: ...cated at the right side of the group link breaker bus tie breaker If this particular controller is not used for the group link function adjust this setpoint to 1 COMMON Group Sync Load ctrl Setpoint V...

Страница 122: ...oup Sync Load Ctrl Range units 0 90 Related FW 3 0 Force value possible YES Description This setpoint adjusts maximum absolute value of difference between actual phase angle between the generator and...

Страница 123: ...neral information about regulation loops and their adjustment Setpoint Freq int Group Sync Load Ctrl Range units 0 100 Related FW 3 0 Description This setpoint adjusts the relative integration factor...

Страница 124: ...amp is adjusted by the setpoint Load ramp in subordinated gen sets Setpoint BCB open del Group Sync Load Ctrl Range units 0 1800 s Related FW 3 0 Force value possible YES Description This setpoint adj...

Страница 125: ...eral information about regulation loops and their adjustment Setpoint Voltage Int Group Volt PF Ctrl Range units 0 100 Related FW 3 0 Description This setpoint adjusts the relative integration factor...

Страница 126: ...een the default names of the force value function blocks associated binary inputs and the default names of the reserved setpoints In other words the setpoint with default name Force value 3 is not rel...

Страница 127: ...Group Force value Range units Related FW 3 0 Description This is one of the 16 setpoints reserved for using as alternative setpoints for the force value functions The alternative setpoint is to be ass...

Страница 128: ...n and renamed in GenConfig See also the input Force value 1 NOTE It is not obligatory to use one of these reserved setpoints for a force value function It is possible to use also any other setpoint or...

Страница 129: ...on NOTE There isn t any relation between the default names of the force value function blocks associated binary inputs and the default names of the reserved setpoints In other words the setpoint with...

Страница 130: ...ue 3 function block Setpoint Force value 12 Group Force value Range units Related FW 3 0 Description This is one of the 16 setpoints reserved for using as alternative setpoints for the force value fun...

Страница 131: ...icular force value function and renamed in GenConfig See also the input Force value 1 NOTE It is not obligatory to use one of these reserved setpoints for a force value function It is possible to use...

Страница 132: ...not obligatory to use one of these reserved setpoints for a force value function It is possible to use also any other setpoint or value with matching dimension and decimal resolution NOTE There isn t...

Страница 133: ...ption This setpoint adjusts the high limit of the value of ExtValue 1 if the value is lowered raised by the binary inputs ExtValue1 up and ExtValue1 down The ExtValue 1 is never raised over this limit...

Страница 134: ...is never lowered below this limit NOTE This limit is not taken into account if the value ExtValue 2 is written remotely from a terminal using the appropriate command ExtValue n NOTE For IS NT only Se...

Страница 135: ...HiLim X Related FW 3 0 Description This setpoint adjusts the low limit of the value of ExtValue 3 if the value is lowered raised by the binary inputs ExtValue3 up and ExtValue3 down The ExtValue 3 is...

Страница 136: ...possible YES Description This setpoint adjusts the reset initial value of the ExtValue 4 This initial value is applied either when the controller is powered on or when the ExtValue 4 is reset by the b...

Страница 137: ...d FW 3 0 Force value possible YES Force value possible YES Description This setpoint adjusts the rate pre second at which the ExtValue 4 is beeing changed while the input ExtValue4 up or ExtValue4 dow...

Страница 138: ...level in of nominal power of gen set for load shedding When the relative load level exceeds this level for more than Ld shed delay time the next load shedding output is closed NOTE Learn more about l...

Страница 139: ...just time period the relative load level must be below the Ld recon level limit to allow reconnection of next load group NOTE Learn more about load shedding in the separate chapter Load shedding Setpo...

Страница 140: ...l 3 Group Timer settings Range units Related FW 3 0 Description This setpoint adjusts the mode of the Timer channel 3 Output from this channel is available in the combined output TimerAct 1 4 NOTE See...

Страница 141: ...l 7 Group Timer settings Range units Related FW 3 0 Description This setpoint adjusts the mode of the Timer channel 7 Output from this channel is available in the combined output TimerAct 5 8 NOTE See...

Страница 142: ...11 Group Timer settings Range units Related FW 3 0 Description This setpoint adjusts the mode of the Timer channel 11 Output from this channel is available in the combined output TimerAct 9 12 NOTE Se...

Страница 143: ...imers Setpoint Timer channel 15 Group Timer settings Range units Related FW 3 0 Description This setpoint adjusts the mode of the Timer channel 15 Output from this channel is available in the combined...

Страница 144: ...ts DISABLED ENABLED Related FW 3 0 Force value possible YES Force value possible YES Description This setpoint is used to enable sending SMS and or e mail alerts when a protection configured as Alarm...

Страница 145: ...point is used to enable sending SMS and or e mail alerts when a BrkOpen CoolDn type alarm occurs See the chapter Alarm management for more information about protection types Setpoint Mains protect Gro...

Страница 146: ...calls SMS Range units DISABLED ENABLED Related FW 3 0 Force value possible YES Description This setpoint is used to enable sending SMS and or e mail alerts when a Sd Override type alarm occurs See th...

Страница 147: ...he selected alert type e g it must contain e mail address if the alert type is e mail See the chapter Alarm messaging for more details Setpoint AcallCH3 Type Group Act calls SMS Range units Related FW...

Страница 148: ...e details Setpoint AcallCH5 Type Group Act calls SMS Range units Related FW 3 0 Description The setpoint is used to specify the alert type of the active calls channel 5 See the chapter Alarm messaging...

Страница 149: ...ll SMS lang Group Act calls SMS Range units 1 7 Related FW 3 0 Description The setpoint specifies in which language the active SMS and e mail messages are issued Adjust the setpoint to the index of th...

Страница 150: ...bled the current season is summer and the controller is located in the northern hemisphere WINTER S The automatic change is enabled the current season is winter and the controller is located in the so...

Страница 151: ...has lowest address If date time is changed at one controller it is automatically updated also in all other controllers in the group NOTE Setpoint with the symbol are synchronized between controllers T...

Страница 152: ...erator active power in phase L2 Value Act pwr L3 Group Bank values Units kW Related FW 3 0 Description Generator active power in phase L3 Value React power Group Bank values Units kVAr Related FW 3 0...

Страница 153: ...kVA Related FW 3 0 Description Generator apparent power in phase L1 Value Appar pwr L2 Group Bank values Units kVA Related FW 3 0 Description Generator apparent power in phase L2 Value Appar pwr L3 Gr...

Страница 154: ...rator load L means inductive load C is capacitive and R is resistive load power factor 1 Value Pwr factor L1 Group Bank values Units Related FW 3 0 Description Generator power factor in phase L1 Value...

Страница 155: ...harmonic waveforms because a simplified method can be used for calculation of it s value However if this simplified method is used for significantly distorted waveforms it may provide inaccurate resu...

Страница 156: ...and the displayed voltage is adjusted by the setpoint VT ratio Value Bank V L3 N Group Bank values Units V Related FW 3 0 Description Bank voltage in phase L3 NOTE The ratio between the voltage measu...

Страница 157: ...V Related FW 3 0 Description Bank voltage between phases L3 and L1 NOTE The ratio between the voltage measured at the input terminals and the displayed voltage is adjusted by the setpoint VT ratio Va...

Страница 158: ...voltages at one moment and expressed in of the nominal voltage NOTE This value can be used for creating the generator voltage unbalance protection using the universal analog protections Value Bank I...

Страница 159: ...io between the voltage measured at the input terminals and the displayed voltage is adjusted by the setpoint Vm VT ratio Value Bus V L2 N Group Bus values Units V Related FW 3 0 Description Bus voltag...

Страница 160: ...lue Bus V L3 L1 Group Bus values Units V Related FW 3 0 Description Bus voltage phase L3 to L1 Value Bus V unbal Group Bus values Units V Related FW 3 0 Description Bus voltage unbalance The value is...

Страница 161: ...value function If the Gen set size optimalization is active then the actual priority is given by the optimalization function Value Act Reserve Group Pwr management Units Related FW 3 0 Description Act...

Страница 162: ...opped This value contains the following Nominal power of gen set which is next to be stopped LdResStp 100 Sum of nominal powers of gen sets loaded in power management except the one which is next to b...

Страница 163: ...the value Engine state Value TotRunPact Q Group Sync Load ctrl Units kVAr Related FW 3 0 Description Sum of reactive power of all banks within the group that are connected to the bus Value TotRunPact...

Страница 164: ...ts of this value show 1 if the bank controller receives messages from the subordinated gen set controller which has address corresponding with the bit position Bit 0 represents address 1 etc This valu...

Страница 165: ...7 32 NOTE The bit which corresponds to the own controller is always set to 1 Value YEL16 Group Gensets Units Related FW 3 0 Description Bits of this value show 1 if the bank controller receives the Ye...

Страница 166: ...Force value Units Related FW 3 0 Description This data object is intended for remote control of the gen set via the communication if some kind of data is to be passed into the controller This object...

Страница 167: ...bject See an example at the object ExtValue1 Value ExtValue3 Group Force value Units Related FW 3 0 Description This data object is intended for remote control of the gen set via the communication if...

Страница 168: ...ls Value CPU Temp Group Analog CU Units C Related FW 3 0 Description Temperature inside the controller on the CPU Value D Group Analog CU Units V Related FW 3 0 Description Voltage measured at the D t...

Страница 169: ...level measurement Value AIN CU 4 Group Analog CU Units configurable Related FW 3 0 Description This is the value of the analog input 4 of the controller Analog inputs are fully configurable so the nam...

Страница 170: ...is a bit array containing status of logical binary outputs 1 16 of the controller Bit0 represents LBO1 bit1 represents LBO2 etc NOTE All terminals display binary values in human readable form from lef...

Страница 171: ...Related FW 3 0 Description This is a bit array containing status of logical binary outputs 49 64 of the controller Bit0 represents LBO49 bit1 represents LBO50 etc NOTE All terminals display binary val...

Страница 172: ...values Value LogBout 7 Group Log bout Units Related FW 3 0 Description This is a bit array containing status of logical binary outputs 97 112 of the controller Bit0 represents LBO97 bit1 represents L...

Страница 173: ...ary values are displayed from right to left Value RemoteControl Group Log bout Units Related FW 3 0 Description This is a bit array containing status of the binary outputs Remote control1 Remote contr...

Страница 174: ...our distributor if you need to retrieve your password Value CAN16 Group Info Units Related FW 3 0 Description Bits of this value show 1 if the bank controller receives messages from the another bank c...

Страница 175: ...s active role in the power management Bit 0 represents address 17 etc This value contains information about controllers with addresses 17 32 Value GL16 Group Info Units Related FW 3 0 Description Bits...

Страница 176: ...t state of the breaker control The text representation of each code can be obtained by the procedure described at the value Engine state Value Timer text Group Info Units Related FW 3 0 Description Co...

Страница 177: ...le in the value NextTime1 4 NOTE More information about timers is available in the chapter General purpose timers Value NextTime5 8 Group Info Units Related FW 3 0 Description This value contains time...

Страница 178: ...the value NextTime9 12 NOTE More information about timers is available in the chapter General purpose timers Value NextTime13 16 Group Info Units Related FW 3 0 Description This value contains time o...

Страница 179: ...gistration denied 3 Can not register no free capacity in the server 4 Can not register other reason 5 Connected registered authorized Value Latitude Group Info Units Related FW 3 0 Description This va...

Страница 180: ...p Statistics Units h Related FW 3 0 Description Engine operation hours counter If an ECU is configured and it provides engine hours value the value is taken from ECU If the value is not available from...

Страница 181: ...alarm WrnServiceTime is issued as soon as the timer counts down to zero Value Service time 2 Group Statistics Units h Related FW 3 0 Description This is maintenance countdown timer 2 The timer is loc...

Страница 182: ...ription This counter counts while the controller is in not ready state i e it can not be started The reason of the not ready state may be either some 2nd level alarm or the controller switched in OFF...

Страница 183: ...ted FW 3 0 Description This is the value of PulseCounter 4 module See the binary input PulseCounter 4 NOTE Available in IS NT only Table of binary input functions Binary input BCB feedback Related FW...

Страница 184: ...wr Management setpoint the gen set excluded from the power management and starts and stops only according to position of this input If the input is not active the gen set is always stopped in AUT mode...

Страница 185: ...gramming is allowed in OFF mode only and GenConfig is not able to switch the controller to OFF mode while MAN mode is forced by this input Binary input REMOTE Remote AUT Related FW 3 0 Description The...

Страница 186: ...aves the gen set in operation If there are any protections still active or not reset in the moment when the input is deactivated the controller will react to them in a standard way Following protectio...

Страница 187: ...e controller has no power supply before the gen set is started It may be also useful in case of testing the gen set or in case of a failure which does not allow the gen set to be controlled by the con...

Страница 188: ...re Starting Idle run Running ForwardSynchro ReverseSynchro Warming Soft load Loaded Soft unld Cooling Stopping Crancking PeakShaveAct Binary input ManualLdRecon Related FW 3 0 Description This input i...

Страница 189: ...rd The function of the input is identical as function of the stop button on the controller front panel The input is enabled only if the setpoint Local Button is set to position EXTBUTTONS or BOTH Bina...

Страница 190: ...wer management is switched to absolute mode LdResStrt 2 and LdResStop 2 if the power management is switched to relative mode CAUTION All controllers cooperating together in Power management must have...

Страница 191: ...s used to activate the load reserve set 4 instead of the set 1 which is active by default The set 4 is adjusted by setpoints LoadResStrt 4 and LoadResStop 4 if the power management is switched to abso...

Страница 192: ...UTION All controllers cooperating together in Power management must have the same minimal running power selected NOTE It is possible to use virtual peripheries for distribution of the binary signal fr...

Страница 193: ...e setpoint Priority ENCODING TABLE PRIORITY INPUT A INPUT B INPUT C INPUT D Default 0 0 0 0 1 1 0 0 0 2 0 1 0 0 3 1 1 0 0 4 0 0 1 0 5 1 0 1 0 6 0 1 1 0 7 1 1 1 0 8 0 0 0 1 9 1 0 0 1 10 0 1 0 1 11 1 1...

Страница 194: ...ty NOTE See encoding table in the description of the input Priority sw A Binary input GroupLink Related FW 3 0 Description This input is used for logical connection and disconnection of the two gen se...

Страница 195: ...input pulses counter are stored in the nonvolatile memory The PulseCounter modules are intended e g for connecting external energy or fuel meters with pulse outputs NOTE Minimal pulse width as well as...

Страница 196: ...al energy or fuel meters with pulse outputs NOTE Minimal pulse width as well as minimal pause between two succesive pulses is 100ms NOTE The counter value can be reset in the InteliMonitor statistics...

Страница 197: ...details about timers Binary input Timer block 5 Related FW 3 0 Description This input is used to disable temporarily the output from the Timer channel 5 NOTE See also the setpoint TimerChannel 5 and o...

Страница 198: ...rily the output from the Timer channel 9 NOTE See also the setpoint TimerChannel 9 and output TimerAct 9 12 NOTE See the chapter Timers for more details about timers Binary input Timer block 10 Relate...

Страница 199: ...TimerAct 13 16 NOTE See the chapter Timers for more details about timers Binary input Timer block 14 Related FW 3 0 Description This input is used to disable temporarily the output from the Timer chan...

Страница 200: ...is input is active the value of ExtValue 1 is contiously beeing decreased at the rate of ExtValue1 rate until it reaches ExtValue1LoLim NOTE If this input is used configured the ExtValue 1 can t be wr...

Страница 201: ...ng decreased at the rate of ExtValue3 rate until it reaches ExtValue3LoLim NOTE If this input is used configured the ExtValue 3 can t be written remotely from a remote terminal using the command ExtVa...

Страница 202: ...reset to it s default value when this input is activated and held there until the input is deactivated The default value is given by the setpoint ExtValue2deflt While the reset input is active The va...

Страница 203: ...er to issue an active call e mail SMS via the channel 1 Type of the channel is to be adjusted by the setpoint AcallCH1 Type This input can be used to inform a remote user about a specific non alarm si...

Страница 204: ...lock to the binary signal mentioned above and select protection type AL indication 3 Configure the binary signal mentioned above onto the logical binary input IssueActCallC3 Binary input IssueActCallC...

Страница 205: ...Local display means that it is connected to dedicated RS485 There is possibility to connect up to 2 external displays in IG NT BB or 1 in IG NT It is possible to connect up to 3 external displays in...

Страница 206: ...itself In such case the controller would issue an Underspeed alarm Connecting this input to an appropriate ECU output which provides information that the engine has been stopped by the ECU prevents t...

Страница 207: ...rriden by value of the alternative setpoint assigned to the Force value 1 block NOTE If there are more than one force value blocks configured onto one setpoint then the highest priority has the block...

Страница 208: ...isplayed in GenConfig in the Force value window at the related setpoint NOTE Watch a training video about force value function here http www comap cz support training training videos NOTE See an examp...

Страница 209: ...re http www comap cz support training training videos NOTE See an example in the description of the binary input Force value 1 Binary input ForceValueIn 5 Related FW 3 0 Description This input activat...

Страница 210: ...ocks configured onto one setpoint then the highest priority has the block with the lowest index i e the first active block according to the list displayed in GenConfig in the Force value window at the...

Страница 211: ...value of the setpoint to which the Force value 10 block is configured will be overriden by value of the alternative setpoint assigned to the Force value 10 block NOTE If there are more than one force...

Страница 212: ...value window at the related setpoint NOTE Watch a training video about force value function here http www comap cz support training training videos NOTE See an example in the description of the binar...

Страница 213: ...iden by value of the alternative setpoint assigned to the Force value 15 block NOTE If there are more than one force value blocks configured onto one setpoint then the highest priority has the block w...

Страница 214: ...ed Binary input Force block 3 Related FW 3 0 Description This is one of three binary inputs used for user defined blocking of protections If the input is active all the protections that have Protectio...

Страница 215: ...ription This is one of three binary inputs Lang sel int A Lang sel int B Lang sel int C used for selecting language of the built in IG NT terminal display As the IS NT does not have built in terminal...

Страница 216: ...sed to be directly attached to the controller or mounted close to it NOTE Using these inputs for language selection is an option only If the inputs are not configured the language can be selected usin...

Страница 217: ...lects the default language of the terminal i e the language which is adjusted in the terminal using it s menus NOTE The reaction on changes of these inputs is delayed about 1 sec to ensure the new com...

Страница 218: ...es the reinitialization of the display Function of the controller is not influenced Binary input Lang sel D 2 C Related FW 3 0 Description This is one of three binary inputs Lang sel D 2 A Lang sel D...

Страница 219: ...nal 3 The terminal 3 is available in IS NT only NOTE Using these inputs for language selection is an option only If the inputs are not configured the language can be selected using the menus on the te...

Страница 220: ...onfigured NOTE Language index 0 selects the default language of the terminal i e the language which is adjusted in the terminal using it s menus NOTE The reaction on changes of these inputs is delayed...

Страница 221: ...lows user to activate chosen function in ScreenEditor tool for GenConfig for particular screen instrument User may choose from the following functions NONE SHOW HIDE No action regarding this screen in...

Страница 222: ...om condition for this swapping function Binary input User mask 3 Related FW 3 0 Description This input allows user to activate chosen function in ScreenEditor tool for GenConfig for particular screen...

Страница 223: ...input is used to adjust the backlight intensity of the IG NT built in terminal display by an analog input e g a potentiometer If this input is configured to a physical analog input or other value the...

Страница 224: ...rminal board between a thermocouple and the IS AIN8 module and there is a significant temperature difference between this terminal board and the module it is necessary to measure the temperature at th...

Страница 225: ...l temperature of the module This analog input is intended for measuement of this thermocouple compensation temperature for the IS AIN8 module with index 4 NOTE Thermocouples without internal compensat...

Страница 226: ...s together with the output Alarm It opens when the output Alarm is opened or Horn reset button is pressed or Horn timeout has elapsed Binary output CommonAlLev 1 Related FW 3 0 Description This output...

Страница 227: ...e end of the Starting period and opens at the end of the Aftercooling period which takes place after the engine has been fully stopped Duration of the aftercooling period is adjusted by the setpoint A...

Страница 228: ...extended to 5sec See timing diagram of all available breaker control outputs in the description of the BCB close open output There are also other outputs availabe for BCB control BCB close open BCB O...

Страница 229: ...scription The output is closed while the actual reserve is above the selected reserve for start Binary output Syst res 1 OK Related FW 3 0 Description The output is closed while the actual reserve is...

Страница 230: ...Related FW 3 0 Description The output is closed while the generator over under voltage alarm is present in the alarm list Binary output Vbus Related FW 3 0 Description The output is closed while the...

Страница 231: ...while there is at least one alarm of the Slow stop type present in the alarm list The alarm can be in any state i e active unconfirmed active confirmed or inactive unconfirmed See the chapter Alarm ma...

Страница 232: ...ted FW 3 0 Description The output is closed for 1s when any alarm of History record type appears See the chapter Alarm management for more information Binary output CommonActLev 1 Related FW 3 0 Descr...

Страница 233: ...activated Binary output HrnResButnEcho Related FW 3 0 Description This output provides 1s pulse when Horn reset button is pressed on the controller front panel or Horn reset button is pressed on any...

Страница 234: ...o on the BCB fdb neg input If only the positive feedback input is used the output mirrors the feedback If both feedbacks are used and they match each other the output indicates the BCB position accord...

Страница 235: ...0 Description This output generates 100ms pulse always when the internal kWh counter incremented Binary output In synchronism Related FW 3 0 Description This output is closed during synchronization w...

Страница 236: ...output Neutral CB C O Related FW 3 0 Description This output is intended for control of the neutral contactor The output provides continuous signal while the neutral contactor has to be closed Use th...

Страница 237: ...redundant controller has not received two consequent messages from the main controller The address of the main controller for the particular redundant one is selected by the the setpoint Watched Contr...

Страница 238: ...ne of the channels is active NOTE See the chapter Timers for more details about timers Binary output TimerAct 5 8 Related FW 3 0 Description This is combined output from timer channels 5 8 The output...

Страница 239: ...only indicates whether the system is able to fulfil it or not Binary output Ready for Load Related FW 3 0 Description This output is closed while the gen set is running it s voltage and frequency are...

Страница 240: ...the prestart phase and remains closed during prestart cranking and starting phases The output is opened either when the bank goes to running phase or when it failed to start See the diagram in the de...

Страница 241: ...lector 1 Related FW 3 0 Description Output is closed or opened according to the setpoint Bin selector 1 NOTE The output is intended for ECU controlled engines to switch on off some particular ECU func...

Страница 242: ...te depends on function assigned to the related button It is possible to lock UserButton commands in configuration to specific user level Buttons 1 8 and 9 16 are locked separately ON Pressing the butt...

Страница 243: ...puls of length of one second to be generated from the moment of button pushing Binary output User Button 3 Related FW 3 0 Description This output can be specified for example on buttons on IV 5 8 or i...

Страница 244: ...Repeated pressing of button during the closed period one second causes issuing another puls of length of one second to be generated from the moment of button pushing Binary output User Button 5 Relat...

Страница 245: ...t is changed to the opposite state PULSE ON Pressing the button issues log binary output User Button X to close for one second NOTE Repeated pressing of button during the closed period one second caus...

Страница 246: ...ned When the output is opened and the button is pressed state is not changed ON OFF Pressing the button changes the state of log binary output User Button X to opened or closed depending on previous s...

Страница 247: ...ON Pressing the button changes the state of log binary output User Button X to closed When the output is closed and the button is pressed state is not changed OFF Pressing the button changes the state...

Страница 248: ...agram in InteliMonitor Its state depends on function assigned to the related button It is possible to lock UserButton commands in configuration to specific user level Buttons 1 8 and 9 16 are locked s...

Страница 249: ...ated from the moment of button pushing Binary output User Button 14 Related FW 3 0 Description This output can be specified for example on buttons on IV 5 8 or in SCADA diagram in InteliMonitor Its st...

Страница 250: ...Repeated pressing of button during the closed period one second causes issuing another puls of length of one second to be generated from the moment of button pushing Binary output User Button 16 Rela...

Страница 251: ...ails about how to control the output from InteliMonitor and the Modbus chapter in the latest communication guide for information about control the output using Modbus Binary output RemoteControl3 Rela...

Страница 252: ...l the output from InteliMonitor and the Modbus chapter in the latest communication guide for information about control the output using Modbus Binary output RemoteControl7 Related FW 3 0 Description T...

Страница 253: ...s enabled and there is not any dongle with PMS feature inserted in the controller The controller is in situation when the load sharing should beeing performed however there is not any dongle with LS f...

Страница 254: ...Sd Stop fail alarm is present in the alarm list This alarm appears when the gen set indicates that it is rotating although it has to be stopped This situation can occur when the gen set starts to rot...

Страница 255: ...ad condition Alarm output Stp GCB fail Related FW 3 0 Description This output is closed while the GCB fail alarm is present in the alarm list Alarm output BOC NCB fail Related FW 3 0 Description This...

Страница 256: ...gen set state running stopped and position of the input Oil press Alarm output OfL StartBlck Related FW 3 0 Description This output is closed while message OfL StartBlck is present in the alarm list...

Страница 257: ...ged in GenConfig Alarm output PLC State 3 Related FW 3 0 Description The output is closed while the alarm generated by the PLC block Force prot 3 is present in the alarm list NOTE The actual text whic...

Страница 258: ...essage number Alarm output UnivState 3 Related FW 3 0 Description The output is closed while the alarm generated by the Universal analog protection where the Message 3 is used is present in the alarm...

Страница 259: ...message number Alarm output UnivState 8 Related FW 3 0 Description The output is closed while the alarm generated by the Universal analog protection where the Message 8 is used is present in the alar...

Страница 260: ...enerated by the Universal analog protection where the Message 13 is used is present in the alarm list See the UnivState 1 for picture how to find the message number Alarm output UnivState 14 Related F...

Отзывы: