IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
55
Enable/Disable protection for
this input
Level 1 protection type
Level 2 protection type
Sensor fail protection ON/OFF
Protection is written to the
history
- alway = when it is trigged
- once = only when it is trigged
for the first time
Defines when the protection
is active
User custom setpoint for
level 1 limit (enables when
level 1 protection type is
selected)
User custom setpoint for
level 2 limit (enables when
level 2 protection type is
selected)
Delay of the protection
evaluation for both levels
(enables when at least one
protection type is selected)
H
INT
Fail Sensor protection (when activated) does not affect the function of the system itself. If you adjust “Active
when” to Under limit + Fls or Over limit + Fls the protection will considered the value that is out of range
(failed sensor) to be under or over limit (depending on the setting) and it will issue corresponding alarm after
the delay of the protection. This can be used for example when the function of the particular sensor
connected to an analog input is crucial for the operation of the system and its failure requires the system to
be affected (open breakers etc.).
Custom configurable protection
Open Protections tab in GenCofig and adjust parameters that are described below.
Existing custom protections
list
Add protection
Delete protection
Select the value for the
protection
Select the protection type
Select if the protection is
under or over limit and if it
should have fail sensor
protection
Defines when the protection
is active
Add new message for
protections
Select message from existing
ones
Select
protection group
(setpoints for
this protection
will be placed in
corresponding
group)
Select wheter the
protection should be
evaluated each 100ms
or each 20 ms.
Protection is
written to the
history
- alway = when it is
trigged
- once = only when
it is trigged for the
first time
Select whether new setpoint should
be created to limit the protection or
an existing one should be used or if
the limit should be constant
Limit the new setpoint value range
Select whether new setpoint should
be created todelay the protection
or an existing one should be used or
if the delay should be constant
H
INT
You need to prepare two separate protections for level 1 and level 2.
Select the value for protection first and then use Wizard
– it will take you through all the steps and help you
adjust them correctly.
Reset Actual Alarms selection
It is possible to determine the behavior of alarms that are in alarm list when Fault Reset button is pressed.
Select behavior with ComProtSetting:ResetActAlarms.