IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
239
Binary output: TimerActiveCom
Related FW
3.0
Description
This is combined output from all timer channels. The output is active if at least one
timer channel is active.
Binary output: SystReady
Related FW
3.0
Description
The output is closed while the group of gen-sets has enough capacity to fulfil the
requested power reserve
. If this output is not closed it means the system has not
enough capacity to fulfil the reserve even if all the gen-sets will run.
N
OTE
:
Fulfiled reserve
means the actual reserve is above the requested reserve for start.
N
OTE
:
This output
do not indicate the requested reserve has been already fulfiled
. It
only indicates whether the system is able to fulfil it or not.
Binary output: Ready for Load
Related FW
3.0
Description
This output is closed while the gen-set is running, it's voltage and frequency are in
limits and the GCB is able to be closed or is already closed.
Binary output: Gen-set active
Related FW
3.0
Description
The output closes at the beginning of the prestart phase and opens after the gen-
set has been fully stopped. If the bank fails to start the output opens after the last
cranking attempt.
N
OTE
:
The output also closes if the engine begins to rotate spontaneously.
Binary output: Operational
Related FW
3.0
Description
The output is closed when the bank is ready for operation or is currently in
operation.
Binary output: Ready
Related FW
3.0
Description
The output is closed while the gen-set is not in operation at the moment, however
it is ready to be put into operation. The output is closed while: