IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
64
Setpoint groups
1.
ProcessControl
2.
Basic settings
3.
Comms settings
4.
ComProtSettings
5.
Analog protect
6.
Bank protect
7.
Pwr Management
8.
Sync/Load ctrl
9.
Volt/PF ctrl
10.
Force value
11.
Load shedding
12.
Timer settings
14.
Date/Time
C
AUTION
!
Do not perform repeated writing of setpoints (e.g. power control from a PLC by repeated writing of baseload
setpoint via Modbus) The setpoints are stored in EEPROM memory, which can be overwritten more than 10
5
times without risk of damage or data loss, but it may become damaged, when allowed number of writing
cycles is exceeded!
H
INT
The descriptions of all available setpoints, values logical binary inputs and logical binary outputs that you can
find in next chapters are common for standard gen-set in MINT application and the Bank Controller. For the
purpose of this document, please consider the term “gen-set” as “Bank Controller”.
Table of setpoints
Group: ProcessControl
Setpoint: #SysBaseLoad
Group
Process Control
Range [units]
0 .. 65000 [kW]
Related FW
3.0
Description
This setpoint is used to adjust the
requested load for the whole gen-set group
in
system baseload
takes proprtionally equal part of this total required value. The number of running
gen-sets is resolved by the
requested total load, gen-sets nominal power and adjusted reserves.
Setpoint: LocalBaseload
Group
Process control
Range [units]
OFF, 1 ..
Related FW
3.0
Force value
YES