P
RINCIPIAL SCHEME OF A SITE IF
N
EUTRAL CONT
=
COMMON
N
OTE
:
As there is always a connection between the N and PE wires at the mains side the
generator neutral contactors are always open when the mains breaker is closed.
Setpoint: WatchedContr
Group
Process Control
Range [units]
0 .. 16 [min]
Related FW
3.0
Description
This setpoint is used at redundant controller to specify the address of the related
main controller in
CAN-based rendundant systems
. Adjust this setpoint to 0 if the
controller is not used as redundant or if
wired rendundancy system
is used.
Group: Basic settings
Setpoint: Nomin current
Group
Basic Settings
Range [units]
1 .. 10000 [A]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used for adjusting the generator nominal current.
The nominal current is used as the basis (100%) for generator thermal-
overcurrent protection (
), and for short current protection (
N
OTE
: