IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
117
Setpoint: ##OverldNextDel
Group
Pwr Management
Range [units]
0 .. 3600 [s]
Related FW
3.0
Description
If the system reserve drops below the start limit for next gen-set the delay
will begin to count down. But if the load raises too quickly it might
happen that the system gets overloaded already before the delay
reaches zero.
This setpoint is used to prevent this situation. If the
counting down (i.e. the condition for starting of next gen-set
based on reserves is
fullfiled
), the total load of running gen-sets reaches 90% of their nominal capacity
and the remaining time of the running timer is higher than
, the
running timer is shortened to the value of
of the next gen-set.
N
OTE
:
The setpoint takes place only in island operation.
Setpoint: #NextStopDel
Group
Pwr Management
Range [units]
0 .. 3600 [s]
Related FW
3.0
Description
This setpoint is used to adjust the delay of stopping the next gen-set when the
actual
load reserve
rises above the adjusted load reserve for stop.
Setpoint: #SlowStopDel
Group
Pwr Management
Range [units]
0 .. 600 [s]
Related FW
3.0
Description
This setpoint is used to adjust how long the particular gen-set will suppress it's
own
Slow stop
alarm to give chance to another gen-set to start and replace the
defective one.
If there isn't any available gen-set to start, the alarm is not suppressed.
Setpoint: #MinRunPower 1
Group
Power Management
Range [units]
0 .. 65000 [kW]
Related FW
3.0
Description
This setpoint is used to adjust certain minimum value of the sum of nominal power
of all running gen-sets. If the function is active, then the gen-sets would not be
stopped, although the reserve for stop is fulfiled, if the total remaining nominal