Binary output: Common Sd
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Shutdown
type
present in the alarm list. The alarm can be in any state, i.e. active unconfirmed,
active confirmed or inactive unconfirmed. See the chapter
Alarm management
for
more information.
Binary output: Common SdOvr
Related FW
3.0
Description
Common output that closes with 2s delay if any Shutdown override-type protection
becomes active. If it is already active and another protection of that type becomes
active, the output is deactivated for 2 seconds and then reactivated again to
inform on this new alarm.
Binary output: Common Stp
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Slow stop
type
present in the alarm list. The alarm can be in any state, i.e. active unconfirmed,
active confirmed or inactive unconfirmed. See the chapter
Alarm management
for
more information.
Binary output: Common Fls
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Sensor fail
type
present in the alarm list. The alarm can be in
any state
, i.e. active unconfirmed,
active confirmed or inactive unconfirmed.See the chapter
Alarm management
for
more information.
Binary output: Common LoP
Related FW
3.0
Description
This IS-NT specific function!
The output is closed while there is at least one alarm of the
Low power
type
present in the alarm list. See the chapter
Alarm management
for more
information.
Binary output: Common OfL
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Off load
type present
in the alarm list. See the chapter
Alarm management
for more information.