IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
123
Force value
possible
YES
Force value
possible
YES
Description
This setpoint adjusts the period of time that the phase angle difference must stay
/-
and voltage difference within
respective breaker, which is actually beeing synchronized, is closed.
Setpoint: Freq gain
Group
Sync/Load Ctrl
Range [units]
0.0 .. 200.0 [%]
Related FW
3.0
Description
This setpoint adjusts the gain factor (P-factor) of the frequency control PI loop.
The integration factor (I-factor) for the frequency loop is adjusted by the setpoint
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
Setpoint: Freq int
Group
Sync/Load Ctrl
Range [units]
0 .. 100 [%]
Related FW
3.0
Description
This setpoint adjusts the relative integration factor (I-factor) of the frequency
control PI loop. The gain factor (P-factor) for the frequency loop is adjusted by the
setpoint
Setpoint: Angle Gain
Group
Sync/Load Ctrl
Range [units]
0.0 .. 200.0 [%]
Related FW
3.0
Description
This setpoint is used for adjusting of the gain factor (P-factor) of the phase angle
P-control loop.
The synchronizing process contains two following steps:
1. The first step is to match the generator frequency to the mains frequency.
In this step the frequency regulation loop (
) is active.
2. The following step is to match the phase angle difference of the mains
and generator voltages to the setpoint
. The angle
regulation loop is active in this step.