IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
139
gen-set) for load reconnection. When the relative load level drops below this level
for more than
time the next load can be reconnected back.
The appropriate load shedding output is either opened automatically when the
condition above is fulfiled (
= ENABLED) or manually by activation of
the input
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
Setpoint: Ld recon del
Group
Load shedding
Range [units]
0 .. 600 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used to adjust time period the relative load level must be below
the
limit to allow reconnection of next load group.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
Setpoint: AutoLd recon
Group
Engine Protect
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Force value
possible
YES
Description
This setpoint selects whether the reconnection of the load occurs automatically
when the relative load level stays below the
or the reconnection must be initiated manually by the input
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
Group: Timer settings
Setpoint: Timer channel 1
Group
Timer settings
Range [units]
[-]
Related FW
3.0
Description
This setpoint adjusts the mode of the
Timer channel #1
. Output from this channel