IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
167
upload the configuration into the controller.
2. Go to InteliMonitor and change the setpoint
Load ctrl PtM
to ANEXT
BASELOAD.
3. Now you have to program your PLC to write requested gen-set baseload
into the Modbus register
ExtValue1
(register number 40392 for IG/IS-NT-
2.4).
Value: ExtValue2
Group
Force value
Units
-
Related FW
3.0
Description
This data object is intended for remote control of the gen-set via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the communication
object number or register number of this particular value object. See an example
at the object
Value: ExtValue3
Group
Force value
Units
-
Related FW
3.0
Description
This data object is intended for remote control of the gen-set via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the communication
object number or register number of this particular value object. See an example
at the object
Value: ExtValue4
Group
Force value
Units
X
Related FW
3.0
Description
This data object is intended for remote control of the gen-set via the
communication if some kind of data is to be passed into the controller.
This object can be written via the communication (e.g. Modbus) without any
limitation. Use GenConfig function Generate Cfg Image to get the communication
object number or register number of this particular value object. See an example
at the object