However, if this simplified method is used for significantly distorted waveforms, it
may provide inaccurate results. This fact causes the controller "power factor"
value may be different from a value measured by another true-rms measurement
device if the waveform contains significant portion of higher harmonic frequencies.
Value: Load char
Group
Bank values
Units
-
Related FW
3.0
Description
Character of the generator load. "L" means inductive load, "C" is capacitive and
"R" is resistive load (power factor = 1).
Value: Pwr factor L1
Group
Bank values
Units
-
Related FW
3.0
Description
Generator power factor in phase L1.
Value: Load char L1
Group
Bank values
Units
-
Related FW
3.0
Description
Character of the generator load in the L1 phase. "L" means inductive load, "C" is
capacitive and "R" is resistive load (power factor = 1).
Value: Pwr factor L2
Group
Bank values
Units
-
Related FW
3.0
Description
Generator power factor in phase L2.
Value: Load char L2
Group
Bank values
Units
-
Related FW
3.0
Description
Character of the generator load in the L2 phase. "L" means inductive load, "C" is
capacitive and "R" is resistive load (power factor = 1).