IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
150
Setpoint: Time Stamp Per
Group
Date/Time
Range [units]
1 .. 240 [min]
Related FW
3.0
Description
The setpoint adjusts the time interval for
Time stamp
records. See also the
setpoint
Setpoint: #SummerTimeMod
Group
Date/Time
Range [units]
DISABLED, WINTER, SUMMER, WINTER-S, SUMMER-S [-]
Related FW
3.0
Description
The setpoint is used to select the mode of automatic daylight saving time change.
DISABLED
The automatic change to daylight saving time and back is
disabled.
WINTER
The automatic change is enabled, the current season is winter
and the controller is located in the northern hemisphere.
SUMMER
The automatic change is enabled, the current season is
summer and the controller is located in the northern
hemisphere.
WINTER-S
The automatic change is enabled, the current season is winter
and the controller is located in the southern hemisphere.
SUMMER-S
The automatic change is enabled, the current season is
summer and the controller is located in the southern
hemisphere.
Setpoint: #Time
Group
Date/Time
Range [units]
[HH:MM:SS]
Related FW
3.0
Description
The setpoint shows the current time from the internal RTC clock of the controller
and can be also used to readjust it.
N
OTE
:
If the controller is connected to other controllers via the CAN2 bus, the setpoints
#Time and #Date are automatically synchronized each hour with the controller
that has lowest address. If date/time is changed at one controller it is
automatically updated also in all other controllers in the group.
N
OTE
:
Setpoint with the symbol # are synchronized between controllers.