IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
69
Setpoint: Derated2 pwr
Group
Process control
Range [units]
0 .. 100 [%]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used for adjusting the final power level for the
Power derating 2
function. The nominal power is not reduced below this setpoint even if the
respective analog input increases further.
See the chapter
Power derating
for details.
Setpoint: Synchro enable
Group
Process Control
Range [units]
NONE, FORWARD, REVERSE, BOTH [-]
Related FW
3.0
Force value
possible
YES
Description
The setpoint is used for enable/disable forward and reverse synchronization.
•
NONE: No synchronizing is enabled.
•
FORWARD: GCB synchronizing is enabled.
•
REVERSE: MCB synchronizing is enabled.
•
BOTH: GCB and MCB synchronizing are enabled.
N
OTE
:
Although synchronizing of the particular breaker is disabled the breaker can be
closed to a "dead" (voltage-free) bus.
N
OTE
:
See table with examples in the description of the setpoint
MFStart enable
.
Setpoint: #Neutral cont
Group
Process control
Range [units]
EACH, COMMON [-]
Related FW
3.0
Description
The setpoint is used for adjusting the behavior of the
according to actual site wiring.
The neutral contactor is used to connect the neutral wire (N) with the protective
wire (PE) in a TN-S system. This connection
must exist in one moment at one
point
of the circuit only.
The
EACH
option should be used if each gen-set has it's own neutral contactor.
Four-pole GCB must be used for this case.