Command Diagnostic Messages
9-111
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C3001 Synchronization and storage failed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The command
P-0-3204, C3000 Synchronize and store safety
technology IDN command
was not or incorrectly executed.
Cause
Remedy
Another safety technology command is still active,
e.g. C07_2 Load defaults procedure command (load
defaults procedure for safety technology) or safety
technology password writing
Wait until active command has been completed and
restart command
P-0-3204, C3000 Synchronize and
store safety technology IDN command
Hardware defect of optional module "safety
technology I/O"
Reset optional module "safety technology I/O" by a
restart. If command error occurs repeatedly, hardware
has to be replaced
C3001 - Attributes
Display:
C3001
Mess. no.:
C3001 (hex)
C3101 Act. modulo value cycle greater than max. travel range
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The command error C3101 is generated when the calculated modulo
value for the actual value cycle is greater than the maximum travel range
(
S-0-0278, Maximum travel range
).
C3101 - Attributes
Display:
C3101
Mess. no.:
C3101 (hex)