Rexroth IndraDrive
Command Diagnostic Messages
9-17
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C4000 Homing procedure command channel 2
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The command
P-0-3228, C4000 Homing procedure command
Channel 2
was started.
See also documentation "Integrated Safety Technology", keyword "Safety
Related Homing Procedure"
C4000 - Attributes
Display:
C40
Mess. no.:
C4000 (hex)
9.2 Command
errors
A command error can not be eliminated via "clear error", but only by
terminating the associated command.
C0101 Invalid parameters (-> S-0-0021)
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Supported by Supply Unit:
HMV01
While the command
S-0-0127, C0100 Communication phase
3
transition check
is executed, internal variables are initialized and the
available parameters are checked (e. g. for validity). An error was
detected during the execution of the command.
Cause
Remedy
Data block elements required in communication
phase 3 are missing or invalid
Write allowed operating data to the respective
parameters(these parameters can be taken from the list
S-0-0021, IDN list of invalid operating data for
communication phase 2
)
A change was made in
P-0-2003, Selection of
functional packages
. Then you failed to reboot
before trying to switch to the operating mode.
Check the content of
P-0-2003, Selection of functional
packages
and reboot (i. e. switch device off and on
again)
A change of functional packages was made in
P-0-2003, Selection of functional packages
which
has an effect on customer- and application-specific
parameter lists (i. e. S-0-0279)
Correct respective list parameters (these parameters
can be taken from the list
S-0-0021, IDN list of invalid
operating data for communication phase 2
).
Problem can also be remedied by loading basic
parameters (
S-0-0262, C07_x Load defaults
procedure command
with respective setting in
P-0-4090, Index for C07 Load defaults procedure
).
Internal data memory defective
Contact our service department
For removing command errors see "Command Errors"
C0101 - Attributes
Display:
C0101
Mess. no.:
C0101 (hex)
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01