7-38
Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F7041 Plausibility error actual position value
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The drive is shut down with velocity command value reset.
The drive automatically switches to safety related standstill and the output
stage is switched off via two channels.
As soon as the axis has stopped the safety door can be opened.
Cause
Remedy
Actual position values determined on channel 1 and
channel 2 are differing
Start command
S-0-0099, C0500 Reset class 1
diagnostics
in order to clear error and then set drive
enable again.
If error occurs repeatedly, replace control section or
entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
F7041 - Attributes
Display:
F7041
Mess. no.:
F7041 (hex)