Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C2905 Programmed firmware defective
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the
P-0-4072, C2900 Command Firmware
update from MMC
an error occurred.
Cause
Remedy
Firmware transfer from MMC was incorrect
Execute
P-0-4072, C2900 Command Firmware update
from MMC
again
Firmware available on MMC is not correct
Use a different MMC with the desired firmware
An error was detected during check of flash
Execute
P-0-4072, C2900 Command Firmware update
from MMC
again.
If error occurs repeatedly, replace control section or
entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
Note:
If the command error occurs during the transmission of the
firmware to an optional module, the respective system error
(F8xxx) is displayed in addition to the command error C2905.
C2905 - Attributes
Display:
C2905
Mess. no.:
C2905 (hex)