9-20
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0105 Maximum length for MDT exceeded
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
S-0-0127, C0100 Communication
phase
3 transition check
an error with regard to the telegram
configuration of the master communication was detected.
Cause
Remedy
In
S-0-0015, Telegram type parameter
telegram
type 7 (configured telegram) was set
Set priority telegram (telegram type = 0..6) in
S-0-0015,
Telegram type parameter
Length of configured data record in MDT that is
determined by
S-0-0024, Config. list of the master
data telegram
exceeds the maximum allowed value
entered in
S-0-0186, Length of the configurable
data record in the MDT
Reduce number of configured parameters in MDT
(
S-0-0024, Config. list of the master data telegram
)
Note:
List parameters are only allowed in the multiplex channel.
For removing command errors see "Command Errors"
C0105 - Attributes
Display:
C0105
Mess. no.:
C0105 (hex)
C0106 Config. IDNs for AT not configurable
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the transition check from communication phase
2 to
communication phase 3 (C0100) an error with regard to the telegram
configuration of the master communication was detected.
Cause
Remedy
in the
S-0-0015, Telegram type parameter
the
telegram type 7 (configured telegram) was set
set priority telegram (telegram type = 0..6) in
S-0-0015,
Telegram type parameter
in
S-0-0016, Custom amplifier telegram
configuration list
there were some parameters
entered that are not contained in
S-0-0187, List of
configurable data in the AT
in
S-0-0016, Custom amplifier telegram configuration
list
those parameters have to be entered that are
contained in
S-0-0187, List of configurable data in the
AT
Note:
List parameters are only allowed in the multiplex channel.
C0106 - Attributes
Display:
C0106
Mess. no.:
C0106 (hex)