Rexroth IndraDrive
Error Messages
7-83
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2018 Device overtemperature shutdown
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Supported by Supply Unit:
HMV01
The heat sink temperature of the device is monitored by a temperature
sensor and a temperature model. When the heat sink temperature has
reached the maximum value, the device is switched off in order to protect
it against destruction.
Note:
Before the error F2018 is triggered, the warning
E2050 Device
overtemp. prewarning
is output for 30 s.
Cause
Remedy
Overtemperature (heat sink) due to overload of
device
Switch drive off and let it cool down. Check mechanical
system and drive dimensioning (working power mustn
’
t
exceed, on average, continuous power of drive).
Ambient temperature too high. Specified
performance data are valid up to an ambient
temperature of 40 C.
Reduce ambient temperature, e.g. by cooling the control
cabinet
Heat sink of device is dirty
Clean heat sink
Convection is prevented by other components or
mounting position of control cabinet
Mount device vertically and provide sufficient space for
ventilating heat sink
Failure of internal blower
If blower fails, replace device or power section
Failure of air conditioning for control cabinet
Check air conditioning of control cabinet
Incorrect dimensioning of control cabinet with regard
to heat discharge
Check dimensioning of control cabinet
See also Functional Description "Current Limitation"
F2018 - Attributes
Display:
F2018
Mess. no.:
F2018 (hex)