Rexroth IndraDrive
Error Messages
7-89
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2033 External power supply X10 error
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
If the X10 interface at the IndraDrive M controller has been equipped with
a digital I/O extension, this requires an external 24 V power supply.
Cause
Remedy
Voltage externally applied is outside of allowed
range [and temporary failures (voltage peaks) are
detected]
Supply interface with controlled power supply unit
At least one of the inputs was connected with
reversed polarity
Check wiring
At least one of the outputs has short circuit
Check wiring
At least one of the outputs is overloaded
Supply motor brake and interface with different power
supply units, especially in the case of long motor cables
F2033 - Attributes
Display:
F2033
Mess. no.:
F2033 (hex)