Rexroth IndraDrive
Command Diagnostic Messages
9-101
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C2301 Error when reading non-volatile memory
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the
S-0-0263, C2300 Load working memory
procedure command
an error occurred.
Cause:
It was impossible to read the active, non-volatile memory [internal flash
memory or MMC (if plugged in)] without error.
Remedy:
Restart the command. If the error occurs again contact the service
department. Have the control section checked for functional safety.
C2301 - Attributes
Display:
C2301
Mess. no.:
C2301 (hex)
C2302 Error when converting parameters
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the
S-0-0263, C2300 Load working memory
procedure command
an error occurred.
Cause:
When reading the parameters from the active, non-volatile memory an
error occurred.
Remedy:
Enter the faulty parameter values correctly by hand and save them again
in the non-volatile memory.
C2302 - Attributes
Display:
C2302
Mess. no.:
C2302 (hex)