Warning Diagnostic Messages (Exxxx)
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E2054 Not homed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Before a motion is carried out a check is run in the case of operating
modes with drive-internal position command value generation (drive-
internal interpolation, drive-controlled positioning and positioning block
mode) to find out whether, with absolute target position preset (
S-0-0258,
Target position
or
S-0-0282, Positioning command value
, or
P-0-4006, Positioning block target position
), the measuring system
used for positioning (cf. operating mode selection) has been homed.
Note:
When the warning E2054 appears, the drive stops or does not
accept the target position or the positioning block. In
parameter
S-0-0012, Class 2 diagnostics
a warning bit is set.
Cause
Remedy
Absolute positioning was started although position
data reference of drive had not yet been established
[drive has not been homed (cf.
S-0-0403, Position
feedback value status
)]
Establish absolute position data reference by starting
command
S-0-0148, C0600 Drive-controlled homing
procedure command
or
P-0-0012, C0300 Command
Set absolute measuring
See also Functional Description "Establishing the Position Data
Reference"