Rexroth IndraDrive
Error Messages
7-77
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2007 Switching to non-initialized operating mode
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When switching the active operating mode the drive was switched to a
non-initialized operating mode.
For the operating modes that can be selected please see Parameter
Description for the operating mode parameters:
•
S-0-0032, Primary mode of operation
•
S-0-0033, Secondary operating mode 1
•
S-0-0034, Secondary operating mode 2
•
S-0-0035, Secondary operating mode 3
Cause
Remedy
Via
S-0-0134, Master control word
(for SERCOS)
or
P-0-4077, Field bus: control word
(for field bus)
an operating mode was selected that had not been
initialized (e.g. S-0-0032="0")
Enter the desired operating mode in the selected
operating mode parameter
See also Functional Description "Operating Mode Selection"
F2007 - Attributes
Display:
F2007
Mess. no.:
F2007 (hex)