Rexroth IndraDrive
Basics on Device Diagnosis
1-17
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Diagnostic
message
number
Error class
Drive reaction
F2xxx
non-fatal error
as set in
P-0-0119, Best possible
deceleration
F3xxx
non-fatal safety
technology
error
as set in
P-0-0119, Best possible
deceleration
F4xxx
interface error
as set in
P-0-0119, Best possible
deceleration
F6xxx
travel range
error
speed command value reset
F7xxx
safety
technology
error
Closed Loop
: speed command value reset
Open Loop
: deceleration under compliance
with
P-0-0569, Maximum stator frequency
change
F8xxx
fatal error
torque disable
F9xxx and
E-xxxx
fatal system
error
torque disable
Fig. 1-15:
Error classes and drive reaction
Errors are not automatically cleared; they have to be cleared by:
•
the control unit by activating the
S-0-0099, C0500 Reset class 1
diagnostics
command or
•
by the user via the control panel
Note:
Some errors can only be cleared in communication phase 2.
If the error status persists the drive controller generates the error
message again.
Note:
Apart from the mentioned error classes that can occur during
operation, errors can occur when the devices are booted and
during firmware download. These errors are not displayed at
the control panel with a diagnostic message number of the
"Fxxxx" pattern, but with a short text. Booting and firmware
download errors are described separately.
Warnings
While in operation the drive controller carries out monitoring functions.
Some monitoring functions depend on the operating mode that is used
and/or parameter settings. If a status is detected that still allows correct
operation but persists, which would then cause an error to be generated,
a warning is generated.
Note:
Some warnings won
’
t result in an error if they are ignored.
Clearing Errors
Booting and Firmware Download
Errors
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01