Rexroth IndraDrive
Error Messages
7-127
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2840 Error supply shutdown
Supported by Supply Unit:
HMV01
Cause
Remedy
A second supply unit or converter connected in
parallel signals a supply error
Remove cause of error at respective supply unit /
converter and clear error
F2840 - Attributes
Display:
F2840
Mess. no.:
F2840 (hex)
F2860 Overcurrent in mains-side power section
Supported by Supply Unit:
HMV01
The current in the power transistor bridge has exceeded the maximum
allowed device peak current. The drive is immediately de-energized, the
motor coasts to stop.
The current in the mains-side power bridge has exceeded the maximum
allowed value. The power supply is switched off.
Cause
Remedy
Short circuit in motor or motor cable
Check motor cable and motor for short circuit
Device defective
Replace device
Current loop parameterized differently (not for
HMV01.1R)
Check current loop parameters to see whether they
differ from the parameters on the motor data sheet;
correct them if necessary
F2860 - Attributes
Display:
F2860
Mess. no.:
F2860 (hex)
F2890 Invalid device code
Supported by Supply Unit:
HMV01
Cause
Remedy
Device defective
Replace device
F2890 - Attributes
Display:
F2890
Mess. no.:
F2890 (hex)
For HCS, HMS, HMD
For HMV01.1R
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01