E8030 Negative position limit exceeded
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The drive provides a function for monitoring an allowed travel range by
means of software limit switches that can be parameterized.
Note:
The travel range monitor has to be activated and
parameterized via
S-0-0049, Positive position limit value
,
S-0-0050, Negative position limit value
and
S-0-0055,
Position polarities
.
The drive reaction (fatal warning or error) in case the travel
range is exceeded has to be parameterized in
P-0-0090,
Travel range limit parameter
.
Cause
Remedy
A command value was set for the drive that causes
an axis position outside the negative travel
range/position limit value
Set command value that leads back to the allowed travel
range.
Contact machine manufacturer in order to find out cause
of incorrect command value
Positive travel range/position limit value incorrectly
parameterized
Check and, if necessary, correct parameterization of
S-0-0050, Negative position limit value
Note:
The
S-0-0057, Position window
parameter is used to realize
a hysteresis function for evaluating the position limit values.
See also Functional Description "Position Limitation/Travel Range Limit
Switch"
E8030 - Attributes
Display:
E8030
Mess. no.:
E8030 (hex)