Command Diagnostic Messages
9-77
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0723 Safety command for load defaults procedure incorrect
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
With the command
C07_2 Load def. proc. com. (load def. pr. for
safety techn.)
the safety parameters of channel 1 are set to default
values and an internal command is started so that channel 2 accepts the
default values. The safety technology is deactivated by the command
because valid safety parameters are no longer available. The safety
technology is in its condition as supplied.
Cause
Remedy
Internal command for channel 2 was incorrectly
executed
Clear command
C07_2 Load def. proc. com. (load def.
pr. for safety techn.)
and then restart it.
If error is signaled again, reset optional safety
technology module (switch control voltage off and then
on again)
Channel 2 is executing another internal command
that mustn
’
t be interrupted
Complete internal command that is still running
Hardware defect on optional safety technology
module
Restart
C07_2 Load def. proc. com. (load def. pr. for
safety techn.)
. If command error occurs repeatedly,
replace control section or entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
C0723 - Attributes
Display:
C0723
Mess. no.:
C0723 (hex)