Rexroth IndraDrive
Diagnostic Messages when Booting the Devices
4-3
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
Load new Param. ?
Brief Description:
MMC plugged, changed or removed => different
parameter file
Cause
Remedy
Active, non-volatile memory (
P-0-4065, Non-volatile
memory active
) has changed while drive was
switched off, because
–
an MMC was plugged (before switching drive off,
device-internal memory had been active) or
–
MultiMediaCard (MMC) was replaced (other MMC
was active) or
–
MMC was removed (before switching drive off,
MMC was active)
Confirm diagnostic message with "ENTER" and start
loading of new parameters
–
or
–
Switch drive off and insert active, non-volatile memory
again that was used before drive was switched off, by
either plugging in MMC / old MMC or removing MMC
again (device-internal memory was active). Then switch
drive on again
End C29
Brief Description:
Command C29 successfully completed
The command
C2900 Command Firmware update from MMC
was
successfully completed. The firmware was copied from the
MultiMediaCard (MMC) to the drive-internal memory.
MMC not correct!
Brief Description:
MMC incorrectly formatted
Cause
Remedy
MMC was not formatted correctly
Switch drive off and plug in appropriate MMC
–
or
–
Switch drive off and format MMC again on PC and plug
it in again
No IBF file or several IBF files on MMC
Switch drive off and plug in appropriate MMC
No appropriate parameter file and retain data file on
MMC
Switch drive off and plug in appropriate MMC
IBF not correct!
Brief Description:
Content of IBF file not correct
Cause
Remedy
IBF file on MMC is not okay
Switch drive off and install MMC with appropriate IBF file
in drive
–
or
–
On PC copy appropriate IBF file to MMC